Cable, Wiring distance, Installation location requirements – Aiphone YAZ-90-3W User Manual

Page 4: Wiring

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

1. Cable

Use twisted pair cable, not straight conductors. (Type CPEV, shielded)
(1) YAZ-90-3W station employs such components as CPU(microprocessor) and 1C chips. Twisted pair

cable must be used to prevent the unit from being interfered by line inductive noises generated by

the surrounding electricai appiiances and from crosstalk and malfunction caused by cable

conductors themselves.

(2) Keep at least 30cm (1 ’) away from other cable, like AC power lines, paging speaker lines or

telephone lines, or provide metal conduit for running cable.

2. Wiring distance

The total wiring distance should not exceed 2.9Km (1.8 mile) with 0.8mm dia. cable (20AWG).

(Ii+l2+i3 +...............

£9

+£io\n the below illustration)

Note; The line loop resistance should not exceed 200 Ohm for communication line between the farthest

stations (Stations 5 and 10) in the system.

4

WIRING ------------------------------------------------------------------------------------------------------------

DIAMETER

00.5mm

00.65mm

0

0.8mm

DISTANCE

1,100m

1,900m

2,900m

AWG

24AWG

22AWG

20AWG

DISTANCE

0.7 mile

1.2 mile

1.8 mile

3, One power supply is required for every 30 Stations

BLOCK A

STATION

1

STATION

30

Q! PS-2420

BLOCK B

STATION

60

DI PS-2420

BLOCK C

STATION

90

I'M

|D|

PS-2420

No.

Of

YAZ-90-3W used

Power supply

required

Location of Power supply

Up to 30 stations

From 31 to 60 stations

From 61 to 90 stations

1 pee

2 pcs

3 pcs

Install a PS-2420 power

supply in the center of each

wiring block of 30 stations.

Notes;

• When power supply is installed in each Block:

#1,2 and 3 as shown in the left illustration, do

not connect terminals +, - between each Block.

• The loop resistance of power supply line

between PS-2420 power supply and the

farthest Station in each Block, should be less
than 20 Ohm.

• When locating power supplies for each Block,

count the paging adaptors as follows;

• one YAW-RB single-zone paging adaptor as

5

X

YAZ-90-3W Stations.

4. Installation location requirements

In general, observe the installation location requirements as stated in PRECAUTIONS section.

When the YAZ system is installed outside the building, such as ski resort and/or between buildings, etc.

the cable has to be buried under ground in metai conduit. Be sure not to run the cable in midair which

can invite lightning surge and causes permanent damage to the YAZ system.

- 4