Bleed-off, Ducted evaporative air conditioning – Bonaire Deluxe Control (LV) - PNE User Manual

Page 7

Advertising
background image

Manual Comfort Control

Ducted Evaporative Air Conditioning

PNE2002 Series Control

Page 7

Bleed-off

All evaporative air conditioners need some water bleed-off to prevent build-up of mineral deposits in
the system. The correct setting of the bleed rate will ultimately govern the life of the unit.

With normal town water supply, bleed rate should be adjusted so that the discharge is not less than
approximately 10 litres per hour. Increased water hardness may require a higher bleed rate and
increased maintenance.

The method for setting the bleed rate is to adjust the patented DIALFLO unit located externally on the
unit.

It is recommended to plumb the bleed-off away from the unit to a down pipe in situations where the
discharge may cause unsightly stains, e.g. Colorbond Roofs.

If dump valve fitted and dumping cycles activated, bleed off may not be required.

Note:

To control water volume to filter pad rotate filter anti-clockwise for more water and clockwise

for less water. To control bleed-off rate rotate bleed dial clockwise for more water and anti-clockwise for
less water.