Processing a type change – Echelon FTXL User Manual

Page 102

Advertising
background image

90

Developing an FTXL Application

} nv_type_category_t;

This enumeration describes the type (signed short or floating-point, for example),

but does not provide information about structure or union fields. To support all
scalar types, test for a type_category value between NVT_CAT_SIGNED_CHAR

and NVT_UNSIGNED_LONG, plus NVT_CAT_SIGNED_QUAD.
The type_length field provides the size of the type in bytes.

Multiple changeable-type network variables can share the SCPTnvType

configuration property. In this case, the application must process all network

variables from the property’s application set, because just as the SCTPnvType
configuration property applies to all of these network variables, so does the type

change request. The application should accept the type change only if all related

network variables can perform the required change.

If one or more type-inheriting configuration properties apply to changing

configuration network variables (CPNVs), these type-inheriting CPNVs also

change their type at the same time. If this type-inheriting CPNV is shared
among multiple network variables, all related network variables must change to

the new type. Sharing a type-inheriting configuration property among both
changeable and non-changeable network variables is not supported.

Processing a Type Change

After validating a type change request, the application performs the type change.

The type-dependent part of your application queries these details when required
and processes the network variable data accordingly.
Some type changes require additional processing, while others do not. For

example, if your application supports changing between different floating-point
types, perhaps no additional processing is required. But if your application

supports changing between different scalar types, it might require the use of

scaling factors to convert the raw network variable value to a scaled value. You
can use the three scaling factors defined in the SCPTnvType configuration

property (scaling_factor_a, scaling_factor_b, and scaling_factor_c) to convert from

raw data to scaled fixed-point data according to the following formula:

(

)

(

)

c

raw

a

scaled

b

+

=

*

10

*

where

raw

is the value before scaling is applied, and

a

,

b

, and

c

are the values for

scaling_factor_a, scaling_factor_b, and scaling_factor_c.

To convert the scaled data back to a raw value for an output network variable,

use the following inverted scaling formula:

c

a

scaled

raw

b

=

10

*

For example, the SNVT_lev_cont type is an unsigned short value that represents

a continuous level from 0 to 100 percent, with a resolution of 0.5%. The actual
data values (the raw

values) are in the variable range from 0 to 200. The scaling

factors for SNVT_lev_cont are defined as a=5, b= -1, c=0.
If the network variable is a member of an inheriting configuration property’s
application set that implements the property as a configuration network variable,