Device Manager User’s Guide

4-7

4-bit Subsystem selection Input Pins

Threaded screw holes for

attaching DM-21 to Base

Plate. Use 8-32, 3/8"

screw, Echelon 205-

0130-01 or equal.

0.180" x 0.280" hole for

attaching Base Plate to
electrical back box or sub-

panel. Use 6-32, flat-head,

3/8" minimum screw.

Wire

Entry

Terminal
Screw,
Tightening
Torque 4
lbs. in.

1 2 3 4 5 6 7 8

9

10 11 12 13 14 15 16 17 18

Model

40111

Writing Space for
Installer.Use Fine Point

Sanford Sharpie Model

30001 Or Equal.

0.230" holes for attaching
Base Plate to electrical
back box or sub-panel.

USE AT LEAST 24 AWG, 90°C RATED

WIRE

Network

16-30VAC or VDC, CLASS 2

UL

c

UL

LISTED

ENERGY MANAGMENT

EQUIPMENT SUBASSEMBLY

178K

+5VDC

GROUND

RESERVED

RESERVED

RESERVED

DB 3

DB 2

DB 1

DB 0

Net 1

Net 1

Net 2

Net 2

Shiel

d

14-30

14-30

14-30

14-30

4-bit

subsystem

selection

input

Figure 4.3 – Type 1 Base Plate, Rear Wiring Panel

The DM-20/21 supports up to 16 subsystems. The subsystem is selected by
setting a 4-bit binary input on the subsystem selection input. Subsystem selection
input pins for the DM-21 are terminals 10, 11, 12, and 13 on the Type 1/1D back-
plate, representing bits 0 to 3 respectively. Subsystem selection input pins for the
DM-20 are pins 14, 12, 9, and 10 of JP1 representing bits 0 to 3, respectively.
Tables 4.4 and 4.5 present the arrangement of jumpers to set the correct
subsystem using the 4-bit subsystem selection inputs.

If only a single database is specified by the DM Pin Usage configuration property,
the DM-20/21 will ignore the subsystem selection setting. The pins/terminals
may then float high or low.

Advertising