Switches and indicator lights – Lingenfelter L460105297 Lingenfelter LNC-003 Dual RPM Launch Controller v2.7 User Manual

Page 4

Advertising
background image

Page 3 of 17

Switches and indicator lights:

Red (Power) LED:

Comes on solid on start-up (power on)

When active RPM is reached, red LED will

blink (even if activation wire is not triggered)

Green (Activation) LED:

Slow blink rate (4 Hz) for Primary Activation

only

Medium blink rate (8 Hz) for Secondary

Activation only

Fast blink rate (16 Hz) for both Primary and Secondary inputs on

Settings:

Controlled by two (2) ten position switches (Primary RPM) and two (2) sixteen position switches

(Secondary RPM limit)

o Two (2) ten position switches for selecting hundreds of RPM (x100) and thousands of RPM (x1000)

for the Primary RPM limit setting

o Two (2) sixteen position switches for selecting hundreds of RPM (x100) and thousands of RPM

(x1000) for the Secondary RPM limit setting. Switch positions after 9 not used.

Notes:

The LNC-003 RPM limiter function will not trigger at RPM levels below 1500 RPM

If both the Primary and the Secondary RPM limit are enabled then the Primary setting is selected

The Primary RPM limit setting can be set higher or lower (or the same as) the Secondary RPM limit

setting

Changes to the switch point settings (RPM, Degrees, Rate) must be done with the ignition off
o The switch positions are only read on start up

Example settings:

1900 RPM activation point for launch control
o Upper (x100) RPM switch on position 9
o Lower (x1000) RPM switch on position 1

• 69

00 RPM activation point for RPM limiter

o Upper (x100) RPM switch on position 9
o Lower (x1000) RPM switch on position 6

0

56

789

1234

0

56

789

1234

100's Switch (x100 RPM)

1000's Switch (x1000 RPM)

RPM Programming

Switches

0

56

789

1234

0

56

789

1234

100's Switch (x100 RPM)

1000's Switch (x1000 RPM)

RPM Programming

Switches

Advertising