OPTI-UPS IS5000LR User Manual

Page 19

Advertising
background image

18

No. Symbol Indication

Description

1.

Over load

The loading exceeds the rating of UPS.

2.

Load level

The higher the loading, the more bars will illuminate.

3.

UPS

is

loaded

When “Green Mode” is enabled, this symbol will display if the loading is

over 30W (default, but adjustable), and disappears when it’s under 25W

(default, but adjustable). Please refer to User’s Manual 4.9. If “Green

Mode” is disabled, the symbol will always display.

4.

Normal mode

1) The sine wave symbol will display steadily without battery symbol when

UPS is in the normal mode.

Battery mode

2) The sine wave symbol and battery symbol will blink when the UPS is in

back-up (inverter) mode.

Test

mode

3) The sine wave symbol will display steadily with blinking battery symbol

when the UPS is in testing mode.

5.

Buck mode

The AVR (Auto Voltage Regulator) is reducing the output voltage of the UPS

(when the input voltage is too high), and the sine wave symbol, as

mentioned in item 4, will also display steadily to indicate that the output is in

the normal mode.

6.

Boost mode

The AVR is increasing the output voltage of the UPS(when the input voltage

is too low), and the sine wave symbol, as mentioned in item 4, will display to

indicate it’s in the normal mode

7.

Timer is enabled

This symbol will show up in the following situations:
1) A turn-on / turn-off schedule has been set using the monitoring

software. Refer to User’s Manual 5.5 and the “Readme” file or “Help”

function of the monitoring software.

2) The Green Mode is enabled and the loading is under 25W (default, but

adjustable). The UPS will turn itself off automatically in 60 seconds.

Refer to 4.9 of User’s Manual.

8.

Thermal

alarm

The temperature inside the UPS is over 55

℃. If the user does not reduce

the load, the temperature will continue to rise and the UPS will shut down

automatically at 60

℃.

9.

Fan is in “High

speed”

The symbol will display whenever the cooling fan is running (or high speed),

and will disappear when it is off (or low speed).

10.

Silence mode

The audible alarm has been silenced. To reset the alarm in Back-up

mode, push the control button (not available during low battery level or

abnormal condition).

11.

IINVERTER

AND UPS fault

The UPS has failed and must be repaired. Contact a qualified service

person.

12.

Battery normal

1) In normal operation, this symbol indicates a charged battery.

Battery

low

2) When the battery charge level is low, the word “LOW” will be added to

the symbol.

13.

Battery

replacement

The battery has failed and must be replaced. The battery is checked each

time the Test Function is executed.

14.

Battery

voltage

level

1) The higher the battery voltage, the more bars will illuminate.
2) When the UPS is charging the battery, the battery symbol and the level

indicator will blink together.

HIGH

LOW

Advertising
This manual is related to the following products: