24

120V Models

230V Models

Nominal Voltage

100V/110V/120V Selectable

220V/230V/240V Selectable

Input Frequency

47Hz ~ 65Hz, 50/60Hz auto-sensing

Efficiency

97% (Normal mode)

Noise Filtering

Full time EMI/RFI filtering

Over current protection

IS1100LT by AC fuse

IS2200LT / IS3000LT

by re-settable over current protector

IS1100LT / IS2200LT by AC fuse

IS3000LT / IS5000LT by

re-settable over current protector

Voltage Range

-20% ~ +22% for selected nominal voltage.

-29% ~ +33% adjustable by using the remote set-up software

AVR Range

(2 Bucks, 2 Boosts)

Enhanced Buck: +15% of selected nominal voltage

Buck mode: +5% of selected nominal voltage

Boost mode: -5% of selected nominal voltage

Enhanced Boost: -12.5% of selected nominal voltage

Surge Protection

IS1100LT 220 Joules

IS2200LT 440 Joules

IS3000LT / IS5000LT 660 Joules

Battery

Battery type

Lead-Acid 25Ah

250Ah

IS1100LT(1100VA/ 660W) : 24Vdc (48Vdc optional)

IS2200LT(2200VA/ 1350W) : 48Vdc (24/36Vdc optional)

IS3000LT(3000VA/ 1800W) : 72Vdc (24/36/48Vdc optional)

Voltage

N / A

IS5000LT(5000VA/ 3200W) : 48Vdc

Typical backup time

No Limit

Charging method

Smart pulse charging with two charging modes Quick charging when battery is

not fully charged, trickle charging when battery is 90% fully charged.

Charging current

11A for IS1100LT / IS2200LT / IS3000LT

30A for IS5000LT(48Vdc)

20A Optional for IS1100LT / IS2200LT / IS3000LT(Below 48Vdc)

P.S. At normal line and normal temperature (Average)

Average charging

voltage for each battery

Quick charging mode 14V maximum.

Trickle charging mode 13.2V ~ 13.9V adjustable with the remote set-up

software.