5.5 Remote Control
The INVERTER AND UPS can be set for daily shutdown/wake up. This command must be set
through the RS-232 interface. When this function is set, the timer inside the INVERTER AND UPS
will begin to run, and the load will be turned off by the shutdown / wake-up schedule. During the
period of turn-off to the next turn-on, the status LED blinks red every 2 seconds. For LCD version,
the time period to next turn-on will be shown on LCD panel by hour (Ref. item 5.2 of LCD
description).

5.5.1 DIP Switch Settings (Available for Tower long run model, IS5000LT, only)

DIP switch setting

DIP 1

DIP 2

230V System

Down Up

200V

Up Up 220V

Up Down

230V

Down Down 240V

DIP setting is valid only when the DIP3=Down.

To apply the other setting on LCD display,

Please refer to 4.11.

DIP 3 for Setting selection UP=invalid for DIP setting / Down=valid for DIP setting

DIP 4 for Green Mode setting UP=Enable / Down = Disable

DIP Switch Settings (for special design of IS5000LT)

DIP 1

DIP 2

Charging

current

Up Up 25%

Down Up 50%

Up Down 75%

Down Down 100%

NOTE of Charging current control

The setting of DIP 1 & 2 is valid only when the DIP3 =

Down.

DIP 3 = Down, UPS mode DIP 3 = Up, Inverter first.
DIP 4 for Green Mode setting UP = Enabled / Down = Disabled

P.S.: The setting active only after the inverter is re-started

5.6 Reset the INVERTER AND UPS
If any abnormal condition occurs, and the item 4.1 ~ 4.7 can not be executed, please unplug the
line cord and push the button for at least 15 sec., which will reset the INVERTER AND UPS.