Module Error Register (MOD_STATUS)

The

Micro800™ 4 Ch Universal Thermistor Input Module is available in only one

configuration: 2080-sc-NTC. The module uses the following parameters:

Bit Number

Description

Notes

0 to 1

These 2 bits define module operation mode:

0: Idle: Module is ready to RUN, and I/O is off.

2: Error: Error happens and I/O is off.

3: Busy: Module is busy, cannot go to RUN,
and I/O is off. See Notes.

3 is not supported

2

This bit defines module user interrupt mode:

0: User Interrupt is disabled.

1: User Interrupt is enabled. See Notes.

Always 0. 1 is not
supported.

3

Reserved

4

SW Error

Trigger condition.
The Watchdog
timer is triggered.

5

ADC Error

Trigger condition.
The ADC
communication
has stopped, or
the ADC has not
sampled data for
a long period of
time.

7

Configuration Error

Wrong bits set in
channel
configuration.

Input Block (0x20 [32] to 0x2F [47])

Register

Address

Comments

Input Data Ch 0

32

Channel 0 through Channel 3 (Signed 16-bit

INT)

Input Data Ch 1

34

Input Data Ch 2

36

Input Data Ch 3

38

RESERVED

40

RESERVED

41 to 47