Spectrum Controls 2080sc-NTC User Manual

Page 26

Advertising
background image

Micro800™ 4 Ch Universal Thermistor Input Module

26

Publication 0100198-01 Rev. A

Environmental

Tests

Industry Standards

Test Level Limits

EFT/B immunity

(Performance
Criteria B)

IEC 61000-4-4

Signal Ports:

± 3 kV @ 5 kHz for 5
minutes, Criteria B
(Marine?)
± 2 kV @ 5 kHz for 5
minutes, Criteria A
(Marine?)

± 2 kV @ 5 kHz for 5
minutes, Criteria B
(standard)

Power Ports:

± 2 kV @ 5 kHz for 5
minutes, Criteria A
(Marine?)

± 2 kV @ 5 kHz for 5
minutes, Criteria B
(standard)

Surge transient
immunity

(Performance
Criteria B)

IEC 61000-4-5

Signal Ports:

± 2 kV line-earth
{CM}@ 2Ω on
shielded ports

Power Ports

± 2 kV CM @ 12

Ω

± 1 kV DM @ 2

Ω

Conducted RF
immunity

(Performance
Criteria A)

IEC 61000-4-6

10 V rms with 1 kHz
sine wave 80% AM
from 150

kHz…80

MHz on signal and
power ports

Magnetic Field

(Performance
Criteria A)

IEC 61000-4-8

30 A rms/m

AC Mains Voltage
Dips, Interruptions
and Variations

IEC 61000-4-11

Follow the 61000-4-
11.

Environmental
Tests

Industry Standards

Test Level Limits

Advertising