Spectrum Controls 2080sc-BAC User Manual

Page 50

Advertising
background image

A-2

Appendix A: Configuration Information

User’s Manual Pub. 0300274-01 Rev. A.0

Environmental Tests

Industry Standards

Test Level Limits

Conducted Emissions

IEC 61000-6-4:2007
Rockwell Document QTP#X0327

Group 1, Class A (AC Mains), 15 0
kHz – 30 MHz

ESD immunity

(Performance

Criteria B)

IEC 61000-4-2

Rockwell Document QTP#X0327

6 kV Indirect (Coupling Plate)

6 kV Contact Discharge ( to points
of initial contact)

8 kV Air Discharge (to points of
initial contact)

Radiated RF

immunity

(Performance

Criteria A)

IEC 61000-4-3: Level 3

Rockwell Document QTP#X0327

10 V/M with 1 kHz sine-wave 80%
AM from 80…2000 MHz
10 V/M with 200 Hz sine-wave 50%
Pulse 100% AM @900 MHz

10 V/M with 200 Hz sine-wave 50%
Pulse 100% AM @1890 MHz

1 V/M with 1 kHz sine-wave 80%
AM from 2000…2700 MHz
(3 V/M goal)

EFT/B immunity

(Performance Criteria
B)

IEC 61000-4-4*

Rockwell Document QTP#X0327

Signal Ports:

± 3 kV @ 5 kHz for 5 minutes,
Criteria B (Marine?)
± 2 kV @ 5 kHz for 5 minutes,
Criteria A (Marine?)

± 2 kV @ 5 kHz for 5 minutes,
Criteria B (standard)

Power Ports:

± 2 kV @ 5 kHz for 5 minutes,
Criteria A (Marine?)

± 2 kV @ 5 kHz for 5 minutes,
Criteria B (standard)

Surge transient
immunity

(Performance Criteria
B)

IEC 61000-4-5

Rockwell Document QTP#X0327

Signal Ports:

± 2 kV line-earth {CM}@ 2Ω on
shielded ports

Power Ports

± 2 kV CM @ 12Ω
± 1 kV DM @ 2Ω

Conducted RF
immunity

(Performance Criteria
A)

IEC 61000-4-6

Rockwell Document QTP#X0327

10 V rms with 1 kHz sine wave 80%
AM from 150 kHz…80 MHz on
signal and power ports

Advertising