Appendix A: Configuration Information

A-3

User’s Manual Pub. 0300274-01 Rev. A.0

Environmental Tests

Industry Standards

Test Level Limits

Magnetic Field

(Performance Criteria
A)

IEC 61000-4-8

Rockwell Document QTP#X0327

30 Arms/m

AC Mains Voltage
Dips, Interruptions
and Variations

IEC 61000-4-11

Rockwell Document QTP#X0327

Follow the 61000-4-11.

Safety Tests and Test Limits

Safety Tests

Industry Standards

cUL

UL 508 Industrial Control Equipment Seventeenth Edition Dated
January 28 1999, with revisions through July 11, 2005 (ANSI/UL 508-
2005) (NRAQ, NRAQ7)

cUL CSA C22.2 No. 142 -M1987 Process Control Equipment May
1987

ULH ANSI/ISA–12.12.01–2007 Non-incendive Electrical Equipment
for Use in Class I, Division 2 Hazardous (Classified) Locations

CULH CSA C22.2 No. 213-M1987 - Non-incendive Electrical
Equipment for use in Class I Division 2 Hazardous Locations - March
1987

CE

CE LVD IEC 61131-2 Programmable Controllers Part 2: Equipment
Requirements and Tests; Second Edition 2003-02, Section 11-14

Performance Requirements

Input Specifications

Inputs per module

2 serial channels, non-concurrent operation

Interface, channel 1

RS-485, configurable during setup

Hardware flow control

None

Baud rates

9600, 19.2 k, 38.4 k, 76.8 k

Interface, channel 2

10/100M Ethernet, auto sensing

Crosstalk

-40 dB, minimum

Input protection

24 VDC continuous.

Power source

3.3 VDC and 24 VDC from backplane, 40 mA from 3.3 VDC
and 50 mA maximum from 24 VDC

Power, RTC Backup

72 hours, minimum

Accuracy, RTC Backup

+1.0,- 3.0 minutes/month.

Power consumption

<45 mA at 3.3 V, <55 mA at 24 V, <1.5 W Total

Inrush current

<500 mA at 3.3 V, <500 mA at 24 V