Spectrum Controls 1794sc-IRT8I User Manual

Page 25

Advertising
background image

Chapter 2: Installation and Wiring

2-15

User's Manual Pub. 0300242‐01 Rev. A

Section 2.6
Module Indicators

The IRT8I module has one status indicator (OK) that is on when power is applied and no
hardware faults are present. See figure below.

Item Description

1 Module

Catalog

Number

2

Module key-switch position

3 Removable

label

4 Power/Status

LED

Table 2-4 (Module Status LED)

Module
State

Condition LED

Color

&

State

New

Power up initialized complete and passed Self-Test. Loads stored
configuration, if it exist. Read Module Information Block. (see notes)

RED, blink
@1 Hz

Not
Config

Module has not received configuration from Master. It can Set and
Get attributes. (see notes)

GREEN,
blink @1 Hz

Idle

Controller in Program mode.
Communications normal

GREEN, solid

Active

Controller in Run mode & Communication Is normal

GREEN, solid

Fault

FlexIO Comm. Fault or PU bit is one and /Fault=0

GREEN, solid

Fatal
Fault

Module fails self tests or detects illegal state transition

RED, solid

1

2

3

4

Figure 2-5