Chapter 3: Configuring the 1794sc-IRT8I for ControlLogix/CompactLogix

3-15

User's Manual Pub. 0300242‐01 Rev. A

The table below describes the input and status mapping.

Table 3-10 (Input & Status)

Usage (16 bit words):

I:0 Channel 0 input Data.
I:1 Channel 1 input Data.
I:2 Channel 2 input Data.
I:3 Channel 3 input Data.
I:4 Channel 4 input Data.
I:5 Channel 5 input Data.
I:6 Channel 6 input Data.
I:7 Channel 7 input Data.
15

14

13

12

11

10

9 8 7 6 5 4 3 2 1 0

S:0 OverRange (CH0/Bit 8, CH1/Bit 9, …)

4

UnderRange (CH0/Bit 0, CH1/Bit 1, …)

S:1

5

User HI Alarms (CH0/Bit8, CH1/Bit9, …)

5

User LO Alarms(CH0/Bit0, CH1/Bit1, …)

S:2 Reserved

CJC

Alarm

6,4

Open Circuit Alarms (CH0/Bit0,

CH1/Bit1, …)

S:3 Reserved

Diagnostic Code (See )

3.5.1 Input Data [Words 0 to 7]

Words 0 through 7 display the digital value for channel inputs 0 through 7, respectively.
Scaling/range is determined by the data format selected. See 3.4.4 for more details.

3.5.2 UnderRange Alarms [Word 8 (Bits 0 to 7)]

The under range flag is set for the associated channel when the channel data value is
below the minimum scale for the selected range.

3.5.3 OverRange Alarm [Word 8 (Bits 8 to 15)]

The over range flag is set for the associated channel when the channel data value is above
the maximum scale for the selected range.

3.5.4 User Low Alarm [Word 9 (Bits 0 to 7)]

The user low alarm flag is set for the associated channel when the channel data value is
below the user low alarm threshold.

3.5.5 User High Alarm [Word 9 (Bits 8 to 15)]

The user high alarm flag is set for the associated channel when the channel data value is
above the user high alarm threshold.

3.5.6 Open Circuit Alarm [Word 10 (Bits 0 to 7)]

If set, the associated channel has detected a shorted or open circuit condition.




4

For the 0 to 20 mA range, a zero reading is valid. Therefore, under range will not trigger at the low

terminus of zero, but will instead trigger when the signal goes negative at or below %2.5 of full scale. 20 –
0 = 20. -0.025 X 20 = -0.5mA.

5

Channel specific range alarms will apply to CJC values if a CJC format is selected for that channel.

6

Channel specific open circuit alarm will not be set if a CJC format is selected for that channel.