A-3

User's Manual Pub. 0300242‐01 Rev. A

±50 mV range

±20uV

±35uV

±10uV

±100 mV range

±40uV

±60uV

±13uV

Resistance Accuracy
with 4.17 Hz filter

Accuracy
Limit At
°25C

Accuracy
Limit At 0-
°55C

Repeatability
Limit
At °25C & 4.17
Hz filter

0-150 ohms range

±0.15
ohms ±0.25

ohms

±10

milliohms

0-1000 ohms range

±1.0 ohms ±2.0 ohms

±100 milliohms

0-3000 ohms range

±1.5 ohms ±2.5 ohms

±100 milliohms

RTD Accuracy
With 4.17 Hz filters

Accuracy
°C
Limit At
°25C

Accuracy
°C
Limit At
0°55C

Repeatability
Limit
At °25C & 4.17
Hz filter

Platinum 385 (100, 200, 500 and 1000
ohms) (IEC751 1983, Amend 2 1995;
JISC 1604 1997)

± 0.7 °C

± 1.2 °C

± 0.1 °C

Platinum 3916 (100, 200, 500 and 1000
ohms) (JISC 1604: 1981)

± 0.6 °C

± 1.1 °C

± 0.1 °C

Nickel 618 (100 ohms) (DIN 43760
Sept. 1987)

± 0.3 °C

± 0.5 °C

± 0.1 °C

Nickel 672(120 ohms) (DIN 43760
Sept. 1987)

± 0.3 °C

± 0.5 °C

± 0.1 °C

Nickel-Iron (518) (MINCO Application
Aid #18,Date 5/90)

± 0.4 °C

± 0.7 °C

± 0.1 °C

Copper 426 (10 ohms) (SAMA RC21-4-
1966)

± 2.4 °C

± 2.8 °C

± 0.1 °C



General Specifications
Voltage range
Supply current

24V dc nom
240 mA @ 24V dc

Dimensions (with module installed in
base)
HxWxD approx.

94 x 94 x 69 mm
(3.7 x 3.7 x 2.7 in.)


Environmental Conditions

Temperature, operating

0…55 °C (-32…131 °F)

Temperature, storage

–40…85 °C (–40…185 °F)

Relative humidity

IEC 60068-2-30
5…95% non-condensing

Vibration

IEC60068-2-6:
5 g @ 10…500Hz

Shock
Operating
Non-operating

IEC60068-2-27:
20 g
25 g

Emissions

IEC61000-6-4
CISPR 11:
Group 1, Class A (with appropriate enclosure)

ESD immunity

IEC 61000-6-2:
6 kV contact discharges
8 kV air discharges