On-Line UPS

User Manual

Models: UPS-1500-OL, UPS-2000-OL, UPS-3000-OL

SX-BDL-1500, SX-BDL-2000

7. Hardware Installation Guide

Inspect the UPS upon receipt. The packaging is recyclable; keep it for reuse or dispose of properly.

A. Safety Information

Information presented here is vital to all personnel. Please read all Safety information.

B. Storage and Transportation

Please handle the UPS and associated equipment with extreme caution since a high amount of energy

is contained in the batteries. Always keep the unit in an upright position as marked on the packaging,

and never drop the unit.

Please adhere to the following instructions if the UPS is not installed immediately:

Store the equipment as is in its original packing and shipping carton.

Do not store in temperatures outside the range of -15°C to +25°C

Ensure that the equipment is fully protected from wet or damp areas and from moist air.

In order to maintain the batteries, the UPS should be recharged every 6 months for at least 8 hours.

If flammable substances such as gases or fumes are present, or if the room is airtight, a hazardous

situation may exist in which no electrical equipment should be operated.

The instructions in this manual explain how to install the UPS safely. Not acknowledging such electrical

hazards may be fatal – keep this manual for future reference.

C. Environment

Ensure that you remember the following when locating the UPS system and battery options:

Avoid extremes of temperature and humidity. Maximum battery life can be attained with a

recommended temperature range of +15°C to +25°C.

Provide protection for the equipment from moisture.

Space and ventilation requirements must be met. Ensure there is 100mm behind and 50mm on the

sides of the UPS for proper ventilation.

Ensure that the front of the UPS remains clear for user operation.

WARNING!

It is strongly recommended that the UPS cabinet not be opened as

components have very high voltage and touching those components may be fatal.

Only a qualified technician or authorized agent may service the unit.

The UPS unit’s output receptacles carry live voltage even when not connected to an

input voltage source. The UPS has its own internal energy source.

Ensure that all environmental concerns and requirements are met according to specifications

listed in this document, otherwise the safety of installation personnel cannot be guaranteed, and

the unit may malfunction.