12. Troubleshooting

Issue

Audible

Alarm

Alarm Description

What You Should Do

The “Input”

letters in the

second row of

the LCD are

flashing

Two Beeps

per second

at startup for

8 total

seconds

The Input Voltage or frequency

may be beyond the normal

acceptable range.

Verify that utility voltage and frequency is

within acceptable range. If so, contact

support.

The “Input”

letters in the

second row of

the LCD are

flashing

One beep

per 2

minutes

Possible mis-wiring AC line and

neutral line

Check wiring of input to UPS (reversed

wiring, etc) Rewire, if necessary

Battery

Indicator

Flashing

One beep

per second

Batteries are undercharged,

disconnected or need to be

replaced.

Check UPS batteries. If necessary

reconnect batteries, wait 12 hours to

charge or replace defective batteries

Utility Normal-

UPS has no

AC input

N/A

Possibility that circuit breaker on

UPS has tripped

Reset circuit breaker

Insufficient

battery run-

time

Once every

4 seconds

in DC mode

“On batt” displayed on LCD

1. If batteries are undercharged let UPS

charge batteries at least 12 hours

2. After charging, if runtime is still

insufficient, replace with new batteries

3. Reduce output load to lengthen runtime

UPS will not

start after

pressing the

“On/Off”

button

N/A

1. Insufficient time for button

depression

2. UPS has no battery connected

3. Battery voltage is too low to

power the load

4. Fault has occurred inside the

UPS

1. Depress the “On/Off” button for at least

three seconds

2. Make sure the batteries are connected

and the connector on the battery cartridge

is “mated” correctly

3. Plug the UPS in, remove all loads, and

allow to charge for 12 hours

4. Contact dealer for service details

Major fault

detection by

the UPS

Constant

beep

Type of fault and fault code

displayed on LCD.

Review abnormal process information

table listed below in this manual and take

appropriate action, If problem does not

resolve contact supplier for service and

provide error code(s)