On-Line UPS

User Manual

Models: UPS-1500-OL, UPS-2000-OL, UPS-3000-OL

SX-BDL-1500, SX-BDL-2000

5.

Connect to Utility Power

For UPS-1500-OL, UPS-2000-OL, UPS-3000-OL Models only:

(For SX-BDL-1500 and SX-BDL-2000 connection installation, skip to instructions below)

A. Plug the UPS into a 3-wire grounded receptacle of proper size per UPS specifications. Make

sure the receptacle is protected by the proper size fuse or circuit breaker, and is not located on

the same circuit with equipment requiring higher amounts of power (e.g. refrigerator, air

conditioner, copier). Avoid using an extension cord to connect the UPS to the input power

receptacle.

N

OTE

: Size of Branch Circuit Over-current Protection – CAUTION – to reduce the risk of

fire, connect only to a circuit provided with 30 amperes maximum branch circuit over-

current protection in accordance with National Electric Code, ANSI/NFPA 70.

For SX-BDL-1500 and SX-BDL-2000 Models only:

(For UPS-1500-OL, UPS-2000-OL, and UPS-3000 connection installation instructions, refer to

instructions above)

A. Connect UPS to SX-1115: Plug the UPS power cord into the SX-1115 (into the receptacle on

the back of the SX-1115). Avoid using an extension cord.

B. Then plug the SX-1115 into a 3-wire grounded receptacle of proper size. Make sure the

receptacle is protected by the proper size fuse or circuit breaker, and is not located on the same

circuit with equipment requiring higher amounts of power (e.g. refrigerator, air conditioner,

copier). Avoid using an extension cord to connect the SX-1115 to the input power receptacle.

C. N

OTE

: Size of Branch Circuit Over-current Protection – CAUTION – to reduce the risk of fire,

connect only to a circuit provided with 30 amperes maximum branch circuit over-current

protection in accordance with National Electric Code, ANSI/NFPA 70.

6.

Connect Telephone or Data Device

A. If you wish to protect a fax, modem or other telephone or data networking device, plug the cable

from the wall into the “IN” jack. Connect the cable provided with the UPS from the “OUT” jack to

the fax, modem, or other networking device. To protect a 10Base-T (UTP) network interface,

obtain and use a UTP cable to connect the “OUT” jack to your computer.

7. Charge Batteries: Once the UPS has been connected to an AC power source the internal charger

will start charging the UPS batteries, at this point the yellow LED is illuminated, and the LCD

displays “UPS OFF”. In this state the output voltage is zero, which means UPS has no output.

Please realize that although you may start using the UPS immediately, maximum back-up time will

still not be available, so it is recommended to charge the batteries for a minimum of 6 hours before

use.