Duct system, Water piping, Duct system water piping – WaterFurnace Versatec Base User Manual

Page 12

Advertising
background image

12

VERSATEC BASE SERIES INSTALLATION MANUAL

An air outlet collar is provided on vertical top flow units

and all horizontal units to facilitate a duct connection.

A flexible connector is recommended for discharge

and return air duct connections on metal duct systems.

Uninsulated duct should be insulated with a minimum of

1-inch duct insulation. Application of the unit to uninsulated

ductwork in an unconditioned space is not recommended

as the unit’s performance will be adversely affected.

If the unit is connected to existing ductwork, check the duct

system to ensure that it has the capacity to accommodate

the air required for the unit application. If the duct is too

small, as in the replacement of heating only systems, larger

Duct System

Water Piping

ductwork should be installed. All existing ductwork should

be checked for leaks and repaired if necessary.

The duct system should be sized to handle the design

airflow quietly and efficiently. To maximize sound

attenuation of the unit blower, the supply and return

plenums should include an internal duct liner of fiberglass

or constructed of ductboard for the first few feet. On

systems employing a sheet metal duct system, canvas

connectors should be used between the unit and the

ductwork. If air noise or excessive airflow is a problem, the

blower speed can be changed.

The proper water flow must be provided to each unit

whenever the unit operates. To assure proper flow, use

pressure/temperature ports to determine the flow rate.

These ports should be located at the supply and return

water connections on the unit. The proper flow rate cannot

be accurately set without measuring the water pressure

drop through the refrigerant-to-water heat exchanger.

All source water connections on commercial units are

fittings that accept a male pipe thread (MPT). Insert the

connectors by hand, then tighten the fitting with a wrench

to provide a leakproof joint. When connecting to an open

loop (groundwater) system, thread any copper MPT fitting

into the connector and tighten in the same manner as

described above.