Typical open loop piping is shown below. Always maintain

water pressure in the heat exchanger by placing water

control valves at the outlet of the unit to prevent mineral

precipitation. Use a closed, bladder-type expansion tank

to minimize mineral formation due to air exposure. Insure

proper water flow through the unit by checking pressure

drop across the heat exchanger and comparing it to the

figures in unit capacity data tables in the specification

catalog. 1.5-2 gpm of flow per ton of cooling capacity is

recommended in open loop applications. Due to only minor

differences in flow rate from low to high, only one solenoid

valve should be used. The valve should be sized for full flow.

Open System - Groundwater Application

Flexible
Duct Collar

Vibration

Absorbing Pad

P/T Plugs

Drain

Low Voltage

to Thermostat

and Valve

Unit Supply

Aux. Heat Supply

Water Out

Water In

Shut Off Valves

Boiler Drains

For HX Flushing

Disconnects

(If Applicable)

Rubber Bladder
Expansion Tank

Solenoid

Valve

Shut Off Valves

(to isolate solenoid

valve while acid flushing)

Strainer

Flow Control

Valve

(on outlet of

Solenoid Valve)

Compressor
Line Voltage

Discharge water from the unit is not contaminated in any

manner and can be disposed of in various ways, depending

on local codes, i.e. recharge well, storm sewer, drain field,

adjacent stream or pond, etc. Most local codes forbid

the use of sanitary sewer for disposal. Consult your local

building and zoning departments to assure compliance in

your area.