Water quality, Condensate drain – WaterFurnace Versatec Base User Manual

Page 13

Advertising
background image

13

VERSATEC BASE SERIES INSTALLATION MANUAL

1/2'' Pitch

Drain

Unit Pitch for Drain

Horizontal Drain Connection (Composite Drain Pan)

Condensate Drain

On vertical units, the internal condensate drain assembly

consists of a drain tube which is connected to the drain

pan, a 3/4 in. PVC female adapter and a flexible connecting

hose. The female adapter may exit either the front or the

side of the cabinet. The adapter should be glued to the

field-installed PVC condensate piping. On vertical units, a

condensate hose is inside all cabinets as a trapping loop;

therefore, an external trap is not necessary.

On horizontal units, a PVC stub or stainless steel tube

is provided for condensate drain piping connection. An

external trap is required (see below). If a vent is necessary,

an open stand pipe may be applied to a tee in the field-

installed condensate piping.

NOTE: All units equipped with electronic condensate

overflow protection.

In ground water situations where scaling could be heavy

or where biological growth such as iron bacteria will be

present, a closed loop system is recommended. The heat

exchanger coils in ground water systems may, over a period

of time, lose heat exchange capabilities due to a buildup

of mineral deposits inside. These can be cleaned, but only

by a qualified service mechanic, as special solutions and

pumping equipment are required. Hot water generator coils

can likewise become scaled and possibly plugged. In areas

Water Quality

Material

Copper

90/10 Cupronickel

316 Stainless Steel

pH

Acidity/Alkalinity

7 - 9

7 - 9

7 - 9

Scaling

Calcium and

Magnesium Carbonate

(Total Hardness)

less than 350 ppm

(Total Hardness)

less than 350 ppm

(Total Hardness)

less than 350 ppm

Corrosion

Hydrogen Sulfide

Less than 0.5 ppm (rotten egg

smell appears at 0.5 ppm)

10 - 50 ppm

Less than 1 ppm

Sulfates

Less than 125 ppm

Less than 125 ppm

Less than 200 ppm

Chlorine

Less than 0.5 ppm

Less than 0.5 ppm

Less than 0.5 ppm

Chlorides

Less than 20 ppm

Less than 125 ppm

Less than 300 ppm

Carbon Dioxide

Less than 50 ppm

10 - 50 ppm

10 - 50 ppm

Ammonia

Less than 2 ppm

Less than 2 ppm

Less than 20 ppm

Ammonia Chloride

Less than 0.5 ppm

Less than 0.5 ppm

Less than 0.5 ppm

Ammonia Nitrate

Less than 0.5 ppm

Less than 0.5 ppm

Less than 0.5 ppm

Ammonia Hydroxide

Less than 0.5 ppm

Less than 0.5 ppm

Less than 0.5 ppm

Ammonia Sulfate

Less than 0.5 ppm

Less than 0.5 ppm

Less than 0.5 ppm

Total Dissolved Solids (TDS)

Less than 1000 ppm

1000 - 1500 ppm

1000 - 1500 ppm

LSI Index

+0.5 to -0.5

+0.5 to -0.5

+0.5 to -0.5

Iron Fouling

(Biological Growth)

Iron, FE

2

+ (Ferrous)

Bacterial Iron Potential

< 0.2 ppm

< 0.2 ppm

< 0.2 ppm

Iron Oxide

Less than 1 ppm, above this

level deposition will occur

Less than 1 ppm, above this

level deposition will occur

Less than 1 ppm, above this

level deposition will occur

Erosion

Suspended Solids

Less than 10 ppm and filtered

for max. of 600 micron size

Less than 10 ppm and filtered

for max. of 600 micron size

Less than 10 ppm and filtered

for max. of 600 micron size

Threshold Velocity

(Fresh Water)

< 6 ft/sec

< 6 ft/sec

< 6 ft/sec

NOTES: Grains = ppm divided by 17

mg/L is equivalent to ppm

2/22/12

with extremely hard water, the owner should be informed

that the heat exchanger may require occasional flushing.

Failure to adhere to the guidelines in the water quality table

could result in loss of warranty.

Units with cupronickel heat exchangers are recommended

for open loop applications due to the increased resistance

to build-up and corrosion, along with reduced wear caused

by acid cleaning.

1.5 in.

1.5 in.

PVC tube stub

PVC coupling

Vent (if needed)

PVC tube stub

1/8 in. per foot

NOTE: UBH006-012 offers a lifted
drain pan that allows the trap to
be installed without additional
ceiling height required.