VERSATEC BASE SERIES INSTALLATION MANUAL

Reference Calculations

Heating Calculations:

Cooling Calculations:

LWT = EWT +

LAT(DB) = EAT(DB) -

LC = TC - SC

S/T =

HR

gpm x 500

SC

cfm x 1.08

SC

TC

HE

gpm x 500

LWT = EWT -

LAT = EAT +

TH = HC + HWC

HC

cfm x 1.08

Legend

ABBREVIATIONS AND DEFINITIONS:

cfm

= airflow, cubic feet/minute

EWT = entering water temperature, Fahrenheit
gpm = water flow in gallons/minute
WPD = water pressure drop, PSI and feet of water
EAT

= entering air temperature, Fahrenheit

(dry bulb/wet bulb)

HC

= air heating capacity, MBtu/h

TC

= total cooling capacity, MBtu/h

SC

= sensible cooling capacity, MBtu/h

KW

= total power unit input, kilowatts

HR

= total heat of rejection, MBtu/h

HE

= total heat of extraction, MBtu/h

HWC = hot water generator capacity, MBtu/h
EER

= Energy Efficient Ratio

= BTU output/Watt input

COP = Coefficient of Performance

= BTU output/BTU input

LWT = leaving water temperature, °F
LAT

= leaving air temperature, °F

TH

= total heating capacity, MBtu/h

LC

= latent cooling capacity, MBtu/h

S/T

= sensible to total cooling ratio