Standard control - panel configuration, Standard control - panel confi guration – WaterFurnace Envision Hydronic (NSW) User Manual

Page 30

Advertising
background image

30

NSW INSTALLATION MANUAL

The control panel allows you to access the service menu

on the unit. The control panel has three 7-segment LED

screens that display the:

• Water temperature

• Configuration menu

There are six (6) LED indicators that indicate when the

SECONDARY OUTPUT is active or the unit is on one of the

following modes:

• Standby Mode

• Heating Mode

• Cooling Mode

• Primary (Master) Mode

The control panel has both UP and DOWN (arrow) buttons

and a MODE button. The UP and DOWN buttons allow you

to change the set point or scroll through the configuration

menu. The MODE button allow you to change mode as well

as enter and exit parameters while in configuration mode.

Control Panel Configuration

The configuration menu allows you to properly set and adjust

all of the unit’s operating parameters to fit your application.

To enter configuration mode and configure parameters,

follow these procedures:

1. Hold down both the UP and DOWN buttons

simultaneously for five seconds, or until the LED screen

displays “LC”.

2. Press the UP or DOWN arrow until “50” is displayed.

3. Press the MODE button. The screen should display “SC

to indicate the controller is in configuration mode.

4. Once in configuration mode, press the UP or DOWN

arrow to scroll through the menu.

5. Press the MODE button to enter the parameter.

(Refer to the parameter table below for a list of

configurable parameters.)

6. Once in the parameter, press the UP or DOWN arrow to

change the parameter.

7. Press the MODE button to return to the main menu.

NOTE: The controller will exit the configuration mode after

30 seconds if no key is pressed.

Standard Control - Panel Confi guration

Control Panel

Changing the Setpoint

1. Pressing the UP or DOWN arrow once will display

the setpoint.

2. The setpoint will flash.

3. When the setpoint is flashing, the UP and DOWN arrow

will change the setpoint by one degree.

4. In Primary mode, the heating temperature setpoint

range is adjustable from 60°F (15.5°C) to 130°F (54.4°C)
with an adjustable deadband range of 1° - 15°F. The
cooling setpoint temperature is adjustable from 25°
(-3.9°C) to 85°F (29.4°C) with a fixed non-adjustable
deadband of 5°F.