2 terminals, 3 terminal configuration, 4 interfaces – Pilz PSSnet GW1 MOD-CAN User Manual

Page 30: 1 canopen interface, Terminals, Terminal configuration, Interfaces, Canopen interface

Advertising
background image

Commissioning

Operating Manual PSSnet GW1 MOD-CAN
1002693-EN-02

30

Spring-loaded terminals:

}

Minimum conductor cross section on field connection terminals = 0.2 mm

2

(AWG24),

}

Maximum conductor cross section on field connection terminals = 2.5 mm

2

(AWG12),

}

Terminal points per connection: 2,

}

Stripping length: 9 mm.

Terminals

The plug-in terminals for the inputs and outputs are not supplied with the system. You can
select between spring-loaded terminals and a screw connection.

Terminal configuration

Module supply

Terminal configuration

X4

4-pin female connec-

tor

1

+24 V infeed for module supply

1 2 3 4

2

0 V infeed for module supply

3

Not connected

4

Functional earth

Terminal configuration

Interfaces

The following minimum requirements must be met:

}

Ethernet standards (min. Category 5) 100BaseTX

}

Double-shielded twisted pair cable for industrial Ethernet use

}

Shielded RJ45 connectors (industrial connectors)

CANopen interface

The connection to CANopen is made via a male 9-pin D-Sub connector.

1

n.c.

6

n.c.

1

5

6

9

. .

.

. .

2

CAN_L

7

CAN_H

3

CAN_GND

8

n.c.

4

n.c.

9

n.c.

5

CAN_SHLD

n.c. = not connected
Please note the following when connecting to CANopen:

}

Only use metal plugs or metallised plastic plugs

}

Twisted pair, screened cable must be used to connect the interfaces

6.2.2

6.3

6.4

6.4.1