Pilz PSSnet GW1 MOD-CAN User Manual

Page 39

Advertising
background image

Technical details

Operating Manual PSSnet GW1 MOD-CAN
1002693-EN-02

39

Environmental data

311602

Climatic suitability

In accordance with the standard

EN 60068-2-30, EN 60068-2-78

Humidity

93 % r. h. at 40 °C

Condensation

Not permitted

EMC

EN 61131-2

Vibration

In accordance with the standard

EN 60068-2-6

Frequency

5,0 - 150,0 Hz

Max. acceleration

1g

Shock stress

In accordance with the standard

EN 60068-2-27

Acceleration

15g

Duration

11 ms

Max. operating height above sea level

2000 m

Airgap creepage

In accordance with the standard

EN 61131-2

Overvoltage category

II

Protection type

In accordance with the standard

EN 60529

Mounting (e.g. cabinet)

IP54

Housing

IP20

Terminals

IP20

Potential isolation

311602

Potential isolation between

CANopen and system voltage

Type of potential isolation

Functional insulation

Rated surge voltage

500 V

Potential isolation between

MODBUS and system voltage

Type of potential isolation

Functional insulation

Rated surge voltage

500 V

Mechanical data

311602

DIN rail

Top hat rail

35 x 7,5 EN 50022

Material

Bottom

PC

Front

PC

Cross section of external conductors with screw ter-

minals

1 core flexible

0,25 - 2,50 mm², 24 - 12 AWG

2 core with the same cross section, flexible with

crimp connectors, no plastic sleeve

0,20 - 1,50 mm², 24 - 16 AWG

2 core with the same cross section, flexible without

crimp connectors or with TWIN crimp connectors

0,20 - 1,50 mm², 24 - 16 AWG

Torque setting with screw terminals

0,50 Nm

Connection type

Spring-loaded terminal, plug in; Screw terminal,

plug in

Cross section of external conductors with spring-load-

ed terminals: flexible with/without crimp connector

0,20 - 2,50 mm², 24 - 12 AWG

Advertising