5 set addresses and transmission rate, 1 set ip address, Set addresses and transmission rate – Pilz PSSnet GW1 MOD-CAN User Manual

Page 32: Set ip address

Advertising
background image

Commissioning

Operating Manual PSSnet GW1 MOD-CAN
1002693-EN-02

32

Set addresses and transmission rate

Set IP address

The first three bytes of the IP address are: 192.168.0. The last byte of the IP address can
be configured.
The subnet mask is: 255.255.255.0.
The last byte of the IP address is configured using the DIP switches. Value range: 1 ...255.

Information
The IP address should

only be set when the module is switched off (no volt-

age applied).
The settings are

only transferred when booting. Any changes made to the

settings during operation will

not be transferred.

There are various options for setting the last byte of the Gateway's IP address.
1. Use of the DHCP Server is enabled

DHCP is automatically enabled on a new module. In this case the IP address is taken
from the DHCP Server, if the DIP switch is set to 0. The module waits for approx. 15
seconds to receive an address from a DHCP Server, in which time it uses the default IP
address 192.168.0.1.
– Set the DIP switch to 0.

2. Setting via the DIP switch

The IP address that is set at the DIP switch is used. DHCP is therefore disabled.
– Set the DIP switch to a value between 1 – 254.

3. Enable DHCP via DIP switch

If the DIP switch is set to 255, DHCP is always used, irrespective of the configuration in
the web server.
– Set the DIP switch to 255.

Example: DIP switch: 00010100 (20 decimal)

(MSB)

(LSB)

1 2 3 4 5 6 7 8

ON

DIP switch setting: 20 (decimal) as the value for the last byte of the IP address

6.5

6.5.1

Advertising