Instruction Manual

9

Fig. 5-3 .- Installation of the current transformer (TC) (external)

The connection point of the TC for a filter bank that compensates an entire installation is after
the installation's mains switch.

To prevent excessive attenuation of the signal, the minimum secondary cable section
(terminals S1, S2) should be at least 2.5 mm2.

Fig. 5-4 .- TC and neutral connection terminals if required

Once the cables are installed, disconnect the jumper connecting terminals S1 and S2 on the
filter bank (see Fig. 5-5)

Fig. 5-5 .- Jumper for short-circuiting the secondary winding of the current transformer (TC).


Any time you wish to change or disconnect a current transformer that is already
installed, it is important to install the jumper connecting S1 and S2.