CIRCUTOR OPTIM-FR Series User Manual

Page 15

Advertising
background image

Instruction Manual

13

Table 7-2.- Tightening torques of the cables to contact terminals

MODEL


Auxiliary (Nm)


POWER (Nm)

GMC-12

1.3

1.6

GMC-18

1.3

2.2

GMC-32

1.3

2.9

GMC-40

1.3

2.9

GMC-50

1.3

4.5

GMC-65

1.3

4.5

GMC-75

1.3

4.5

GMC-85

1.3

4.5

GMC-150

1.3

9

Table 7-3.- Tightening torques of the cables to reactor terminals.

Reactor

Connection

Terminal (Nm)

R-5-400

Terminal

1.83

R-10-400

Terminal

1.83

R-15-400

Terminal

1.83

RB-20-400

Flat strip

6.2

RB-25-400

Flat strip

6.2

RB-30-400

Flat strip

15.2

RB-40-400

Flat strip

15.2

RB-50-400

Flat strip

30

RB-60-400

Flat strip

30

RB-80-400

Flat strip

30

7.2.3 Key points for inspecting contactors.

Check that the plastic parts are not blackened and do not show signs of burning or hardening.

Check that the head is properly inserted

Check the tightness of cables and terminals, as shown in table 7-2

The terminals must be clean.

If the filter bank includes RD discharge resistances, check they are in good condition (that they
are not open or show signs of burning).

Fig. 7-1 .-

Connection of the discharge resistances

Cleaning the contactors: In dirty environments (dust, sawdust, metal trimmings, etc).
Periodically vacuum the dust and solid remains. There is no estimated time frame for cleaning,
it depends on the amount of dirt that penetrates the filter bank's cabinet.