Wiring cont. 4. setup – CP Electronics MWS5 + slim line PSU User Manual

Page 6

Advertising
background image

page 6

1. Connect the power supply via the terminal block on the power supply unit as shown overleaf. Live

supply to the L terminal, Neutral to the N terminal and the load to the LIVE OUT (L/out) terminal.

2. Connect the sensor head to the power supply unit using the RJ11 connector, ensuring it ―clicks‖ in

place.

3. In the case of dimming applications, connect the D+ (dimming up) and D

_

(dimming down) connections

to the corresponding terminals on the luminaire dimming ballast.

4. On power up, the load should come on immediately.

5. Vacate the room or remain very still and wait for the load to switch off (on the factory preset, this

should take approximately 15 minutes, but the timing out period can be adjusted down to 1 minute to
help speed up the setup procedure — please see next section for details on set-up & adjustment).

6. Check that the load switches on when movement is detected.

3. Wiring cont.

4. Setup

Positioning

The detector should be sited so that the occupants of the room fall inside the detection pattern shown
in section 6 (page 11). Please note that when ceiling mounting, the recommended ceiling height of the
sensor head is 2.4m. Note that the lower the sensor is installed the smaller the detection range will be,
subject to the parameters shown on the diagram.

Avoid direct sunlight entering the sensor.

Do not site within 1m of forced air heating or ventilation.

Do not fix to a vibrating surface.

Avoid metallic objects directly in front of the sensor head.

Do not fit to a suspended luminaire.