5. Programming

All the following functions can be programmed using the remote control DD-LCDHS handset:

1. Detector Parameters (factory default in brackets):

1.1

Time adjustment (20 min)

10 seconds to 99 minutes time delay (select 0 for 10 second

delay – use for commissioning only).

1.2

Sensitivity On

Sensitivity level when the detector is already operational

adjustable between 1 (min.) and 9 (max.)

1.3

Sensitivity Off

Sensitivity level for switching the detector on – adjustable

between 1 (min.) and 9 (max.).

1.4

Power Up On (Y)

Select No for a 30 second delay on start up. If Yes is selected,

there will be no delay on start up and the detector will always

power up detecting.

1.5

Walk Test (N)

An LED behind the detector lens will flash to show movement

has been detected (use for commissioning).

1.6

Disable Detector (N)

Disables detection, leaving the relay output permanently off

with the dimming output operational. This mode is used when

the unit is for maintained illuminance only.

1.7

Factory Default

Restores factory default settings.


2. Modes (factory default in brackets):

2.1 Channel Modes

2.1.1 Switch only

N/A

2.1.2 Switch and dim together (default) The detector will switch and dim the lighting together.
2.1.3 Switch and dim separate

N/A


3.

Switching Channel 1 functions (factory default in brackets):

(-DD & -AD—this channel controls the relay output, whereas Channel 2 controls the dimmed

output. The parameters below should be programmed as well as the corresponding parameter

on Channel 2)

3.1 Presence detection

Auto switch on with detection, auto off after movement ceases

and time delay ends.

3.2 Switch level on (9)

Lux level setting to prevent the luminaires being switched on if
the ambient light level is sufficient (adjustable between 1

and 9). The luminaires will always be switched on at level 9.

For a higher resolution of ‗switch level on‘ a scale of 101-199
is available in the ‗Special menu‘.

3.3 Switch level off (9)

Lux level setting to switch the luminaires off during occupancy
if the ambient light level goes above the setting (adjustable

between 1 and 9). Level 9 will always keep the lights on. This
setting can be used for ―window row switching‖.

For a higher resolution of ‗switch level off‘ a scale of 101-199
is available in the ‗Special menu‘.

Advertising