4.1. Configuration of the PER 610 module


PER610 is a six-channel relay switching unit for loads up to 10 A per channel. There are all
changeable parameters in the configuration window of the module. The parameters in the upper part
of the window are shared by all channels of the module.

Fig. 10


4.1.1. PER 610 parameters description


Interface address 0-15 address of the module. The addresses of all channels of this module are

based on this value.

Bank 0-9 module group
Filter 0-180 msec. minimum time of pressing the button for the press to be valid.
Long press 0-900 msec. If the time of pressing the button is longer than this value, the press is

interpreted as a long press.


The following parameters can be set for each channel independently:

Function mode selection for control relay by its buttons

no action - buttons are disabled.
coded - Each press causes the negation of the relay state (switched on/off)
relay - When button is pressed, the output is on, otherwise it is off.
system on - When pressed, the relay switches on; it can be switched off only by a command

through serial line.