4.5. Configuration of the PEF 200 module


PEF200 is a two-channel interface for fluorescent lamp dimming ballasts with DSI control signal
(TRIDONIC, ZUMTOBEL).

Fig. 15


4.5.1. PEF 200 parameters description


Interface address 0-15 address of the module. The addresses of both channels of this module

are based on this value.

Bank 0-9 module group
Filter 0-180 msec. Minimum time of pressing the button for the press to be valid.
Long press 0-900 msec. If the time of pressing the button is longer than this value, the press is

interpreted as a long press.


The following parameters can be set for each channel independently:

Function mode selection for control dimmers by it’s buttons

no action - buttons are disabled.
toggle - switch outputs between maximum and minimum values.
solid state - if no button is pressed, the output has the minimum value. If one button is

pressed, the output has the value entered in the parameter Intermediate. If both buttons are
pressed, the output has the maximum value.

dimmer – a short press of the UP/DOWN button changes the output value to

maximum/minimum at the speed set in the parameter Short press fade. A long press makes
the output dim up/down at the speed set in the parameter Long press fade. A release of the
button makes it stop at the currently reached value. If button down is held, the value does not
go all the way to 0%, but stops at 1 %. For a total switch-off use repeated quick press.

Short press fade - speed of dimming in case of normal button press, 0-99.9 sec.
Long press fade - speed of dimming in case of long time button press, 0-99.9 sec.
Minimum - minimum output value, 0-99 %.
Maximum - maximum output value, 0-99 %.
Intermediate - intermediate output value, 0-99 % for solid state mode.

User Manual PEX Software