Eas use with digit alert systems dasdec – Monroe Electronics R197AV User Manual

Page 20

Advertising
background image

Configuring the DASDEC

Each switch of the R197AV is network controlled by the DASDEC over a TCP/IP (Ethernet)
connection. Each of the R197AV program switches is tied to a Net GPIO relay control set-
ting in the DASDEC. Setting NET GPIO Output Relay 1 will close the Channel 1 AES switch;
NET GPIO Output Relay 2 will close Channel 2 AES switch, etc. When any switch is closed
the incoming analog audio to the Master input is digitized and output on each closed channel.

1. Once the R197AV is configured with the

proper network settings connect it to a
network where the DASDEC can “see”
the device – i.e. the same network or, if
the DASDEC has the EXP-3NIC or
EXP-3NICGIG Ethernet expansion
directly (via a crossover cable to one of
the expansion ports). Note the port
numbers must match the configuration
settings. Refer to the picture for port
numbering

.

2. Log onto the DASDEC box either remotely or locally from the web browser interface. The
default is “Admin” as the User Name and “dasdec” as the password. (note: User Name and
Password are case-sensive)

3. If the R197AV is on a common network (ie through an Ethernet switch to the DASDEC skip
to Step 12. If the R197AV is connected to one of the other Ethernet ports 2 - 4 follow the steps
below to ensure the network settings are correct.

4. Go to Setup > Network > Configuration

5. Enable the network inteface which is connected to the R197AV by selecting the box next to
the [number] Network Interface.

EAS use with Digit Alert Systems DASDEC

20

Advertising