Prism ii setup instructions – Auto-Zone Control Systems CommLink IV Technical Guide, Installation Instructions for the CommLink IV Communications Interface (Version 01E) User Manual

Page 13

Advertising
background image

CommLink IV Technical Guide

13

Operator Interface

8. In the Network Confi guration selection box, select the type

of CommLink you are using. This will be either Multiple
Loop Confi guration or Single Loop Confi guration.

9. Click

<Exit>

to close out of the Job Sites Window.

10.

Click the

<OFFLINE>

button to go

<ON LINE>

.

11. From the

<Communications>

menu, select

<Search

for Units>

.

12. The Search for Installed Units Window will pop up. Click

<Start Search>

to initiate an automatic detection of all

installed controllers on your system.

Prism II Setup Instructions

13. If everything is working correctly, Units Found on this

Loop should increment.

14. If Units Found on this Loop stays at zero, check the wiring

to the CommLink IV and the AHU/RTU Controllers and/
or read through these directions again to make sure all steps
were followed.