Installation – Avalon Firestyles Cottage User Manual

Page 10

Advertising
background image

10

Installation

(for qualified installers only)

Travis Industries

93508113

4 020325

Chimney Requirements

Chimney connector must be a minimum 24 MSG black or 26 MSG blued steel

Use 6" diameter type HT chimney from one manufacturer (do not mix brands). Chimney must be
used from the first floor or wall penetration to the chimney cap.

Chimney connector and chimney must be fastened to the stove and each adjoining section

Follow the chimney manufacturer's clearances and requirements

Use the chimney manufacturer's fire stops, attic guards, roof supports, and flashings when
passing through a ceiling or thimble when passing through a combustible wall

No more than 180

o

of elbows (two 90

o

elbows, or two 45

o

& one 90

o

elbow, etc.)

NOTE: Additional elbows may be allowed if draft is sufficient. Whenever elbows are used the draft is

adversely affected. Additional chimney height may be required to boost draft.

Chimney Cap
(See the section
"Chimney Termination
Requirements" for
more details)

Factory Built
Chimney
Sections

Minimum Air Space to
Combustibles (See
Chimney Manufacturer's
Instructions - usually 2")

Floor Penetration
Equipment (Attic
Radiation Shield with
Chimney Support)

Reduceced
Clearance
Chimney
Connector
Sections

Roof Penetration Equipment
(Roof Radiation Shield,
Flashing, Storm Collar)

}

}

Floor
Protection

Stove Clearance
(as outlined in this manual)

}

Standard residential installations with
reduced clearance connector may use the
clearance determined by the manufacturer
of the connector for the connector to wall
clearance or the clearance listed in this
manual.

Mobile home installations must use the
the reduced clearance connector
clearances listed in this manual under
“Additional Requirements for Mobile Home
Installations”.

Minimum System 15'
Maximum System 33'

D r a f t i n g
Performanc
e

This appliance relies upon natural draft to operate. External forces, such as wind, barometric
pressure, topography, or factors of the home (negative pressure from exhaust fans, chimneys,
air infiltration, etc.), may adversely affect draft. Travis Industries can not be responsible for
external forces leading to less than optimal performance.

Standard residential installations may use single-wall connector (Mobile-Homes may

n o t )

Standard residential installations with reduced clearance connector may use the clearance
determined by the manufacturer of the connector for the connector to wall clearance or the clearance
listed in this manual. Offsets must be used to maintain the stove to wall clearance. Mobile homes
must use the clearances listed in this manual under "Additional Requirements for Mobile Home
Installations".