BE1-50/51B-233 General Information

1-3

Time characteristic curve constants are listed in Tables 1-2 and 1-3. Constants have been selected to
conform to the characteristics of electromechanical relays over a range of pickup multiples from 1.3 to 40.
Values of the constants are provided for use in computer relay setting software. Timing accuracy is

1

cycle,

2 percent of time to trip.

Table 1-2. Time Characteristic Curve Constants with SW3-3 Open (Off)

Curve Type

Constants

BE1 Similar

To

Figure

Number

A B C N K R

S ABB

CO-2

A-1 0.2663

0.03393

1.000

1.2969

0.028

0.500

L ABB

CO-5

A-2 5.6143

2.18592 1.000 1.000 0.028 15.750

D ABB

CO-6

A-3 0.4797

0.21359 1.000 1.5625 0.028 0.875

M ABB

CO-7

A-4

0.3022

0.12840

1.000

0.5000

0.028

1.750

I ABB

CO-8 A-5 8.9341

0.17966

1.000

2.0938

0.028

9.000

V ABB

CO-9

A-6 5.4678

0.10814

1.000

2.0469

0.028

5.500

E ABB

CO-11

A-7

7.7624

0.02758

1.000

2.0938

0.028

7.750

B BS142-B

A-8

1.4638

0.00000

1.000

1.0469

0.028

3.250

C BS142-C

A-9

8.2506

0.00000 1.000 2.0469 0.028 8.000

F None

§

N/A 0.0000

1.00000

0.000

0.0000

0.000

1.000

Table 1-3. Time Characteristic Curve Constants with SW3-3 Closed (On)

Curve Type

Constants

BE1 Similar

To

Figure

Number

A B C N K R

S

GE IAC 55

A-10

0.0286

0.0208

1.000

0.9844

0.028

0.0940

L

GE IAC 66

A-11

2.3955

0.00002 1.000 0.3125 0.028 7.8001

D ABB

CO-6

A-3 0.4797

0.21359 1.000 1.5625 0.028 0.8750

M

ABB

CO-7

A-4

0.3022 0.12840 1.000 0.5000 0.028 1.7500

I

GE IAC 51

A-12

0.2747

0.1042

1.000

0.4375

0.028

0.8868

V

GE IAC 53

A-13

4.4309

0.0991

1.000

1.9531

0.028

5.8231

E

GE IAC 77

A-14

4.9883

0.0129

1.000

2.0469

0.028

4.7742

B

BS142-B

A-8

1.4636 0.00000 1.000 1.0469 0.028 3.2500

C BS142-C

A-9

8.2506

0.00000 1.000 2.0469 0.028 8.0000

F

None

§

N/A

0.0000 1.00000 0.000 0.0000 0.000 1.0000

Notes for Tables 1-2 and 1-3
 BE1 Curve Types:

S: Short Inverse

V: Very Inverse

L: Long Inverse

E: Extremely Inverse

D: Definite Time

B: BS142 Very Inverse

M: Moderately Inverse

C: BS142 Extremely Inverse

I: Inverse

F: Fixed Time Delay

† Figure numbers refer to the characteristic curves located in Appendix A, Time Characteristic Curves.

‡ Curves B and C are defined in British Standard BS142 and IEC Standard IEC 255-4.

§ Fixed time delay, adjustable from 0.1 to 9.9 seconds.

Integrating Reset

Reset begins when the current drops below 95% of pickup. Integrating reset simulates the disk reset of
electromechanical relays. BE1-50/51B-233 relays provide the integrating reset function even when input
current falls to zero.