Test procedure, Time pickup test, Inst pickup test – Basler Electric BE1-50/51B-233 User Manual

Page 39: Test procedure -3

Advertising
background image

NOTE

When testing TIME overcurrent functions, INST PICKUP settings of 00 will affect
the calibration of the TIME functions. TIME PICKUP settings of 00 also affect
INST functions.

Test Procedure

The following tests are performed to verify functionality of the BE1-50/51B-233 overcurrent relay. The
TIME and INST output contact terminals are strapped together. Therefore it is necessary to disconnect
specific wires during the TIME and INST pickup tests. This verifies the proper functionality of the TIME
and INST elements.

NOTE

Observe all applicable electrostatic discharge (ESD) precautions when handling
the relay draw-out assembly.

TIME Pickup Test

Perform preliminary setup:

 Connect test setup as shown in Figure 5-1.
 Insure that SW3 switches are set: SW3-1 to OFF, SW3-2 to OFF, SW3-3 to ON and SW3-4 to

ON.

 Set TIME DIAL to 0.0.
 Set CURVE to S
 Set TIME PICKUP to 0.5.
 Set INST PICKUP to 90.

Step 1. Slowly increase current to terminals 8 and 9. PICKUP LED should turn RED at a maximum input

current of 0.550 ampere.

Step 2. Decrease input current until PICKUP LED turns GREEN then OFF.

Step 3. Set TIME PICKUP to 2.2.

Step 4. Slowly increase current to terminals 8 and 9. PICKUP LED should change from GREEN to RED

at an input current of 2.131 to 2.269 amperes.

Step 5. Decrease input current until PICKUP LED turns OFF.

INST Pickup Test

Perform preliminary setup:

 Connect test setup as shown in Figure 5-1.
 Insure that SW3 switches are set: SW3-1 to OFF, SW3-2 to OFF, SW3-3 to ON, and SW3-4 ON.
 Set TIME DIAL to 0.0.
 Set CURVE to S
 Set TIME PICKUP to 15.9.
 Set INST PICKUP to 01.

Step 1. Slowly increase current to terminals 8 and 9. INST contacts should close at an input current of

0.955 to 1.045 amperes.

Step 2. Decrease input current until INST output contacts open.

Step 3. Set INST PICKUP to 08.

Step 4. Slowly increase current to terminals 8 and 9. INST contacts should close at an input current of

7.815 to 8.185 amperes.

Step 5. Decrease input current until INST output contacts open.

9252000897 Rev B

BE1-50/51B-233 Testing