Time dial test, Target test, Manual trip test – Basler Electric BE1-50/51B-233 User Manual

Page 40

Advertising
background image

Time Dial Test

Perform preliminary setup:

 Connect test setup as shown in Figure 5-1.
 Insure that SW3 switches are set: SW3-1 to OFF, SW3-2 to OFF, SW3-3 to ON, and SW3-4 ON.
 Set TIME DIAL to 4.5.
 Set CURVE to S
 Set TIME PICKUP to 1.0.
 Set INST PICKUP to 90.

Step 1. Prepare to apply 1.5 amperes input current to terminals 8 and 9 and record the elapsed time from

when current is applied until TIME output contacts close.

Step 2. Apply the current (step from 0 to 1.5 amperes) and record the elapsed time. Elapsed time should

be 0.345 to 0.424 seconds. (This tolerance is greater than ±2 % because it is the accumulation of
both pickup and timing tolerances.)

Step 3. Remove input current.

Target Test

Perform preliminary setup:

 Connect test setup as shown in Figure 5-2.
 Insure that SW3 switches are set: SW3-1 to OFF, SW3-2 to OFF, SW3-3 to ON, and SW3-4 ON.
 Set TIME DIAL to 4.5.
 Set CURVE to S
 Set TIME PICKUP to 1.0.
 Set INST PICKUP to 90.

Step 1. Set voltage source to provide a target current of 1.0 ampere.

Step 2. Apply 5 amperes input current to terminals 8 and 9. Check that the TIME target operates.

Step 3. Remove input current and reset target.

Step 4. Set TIME PICKUP to 15.9 and set INST PICKUP to 01.

Step 5. Set voltage source to provide a target current of 1.0 ampere.

Step 6. Apply 5 amperes input current to terminals 8 and 9. Check that the INST target operates.

Step 7. Remove input current and reset target.

Manual Trip Test

Perform preliminary setup:

 Connect test setup as shown in Figure 5-2.
 Insure that SW3 switches are set: SW3-1 to OFF, SW3-2 to OFF, SW3-3 to ON, and SW3-4 ON.
 Set TIME DIAL to 4.5.
 Set CURVE to S
 Set TIME PICKUP to 1.0.
 Set INST PICKUP to 01.

WARNING!

Trip circuit voltage is present at the front panel test points. When shorting the test
points, use insulated jumpers to avoid contact with these voltages.

Step 1. Set voltage source to provide a target current of 1.0 ampere.

Step 2. Apply 0.9 ampere input current to terminals 8 and 9. (0.9 ampere provides input power but stays

below pickup.)

Step 3. Connect a jumper between TIME MANUAL TRIP test points. Check that TIME target operates.

5-4

BE1-50/51B-233 Testing

9252000897 Rev B

Advertising