O figure 5-2 – Basler Electric BE1-59NC User Manual

Page 36

Advertising
background image

Step 14. Starting at maximum CW, slowly turn OVERVOLTAGE 2 PICKUP adjust potentiometer R43

CCW until OVERVOLTAGE 2 PICKUP LED just illuminates.

Step 15. Set OVERVOLTAGE 2 TIME DIAL to 001 and apply to case terminals 6 and 7, a voltage that is

10% greater than the value applied in Step 13.

Step 16. Monitor the output terminals indicated in Figure 5-1 for OVERVOLTAGE 2. Remove, then

reapply the overvoltage at case terminals 6 and 7. Observe the time registered by the counter.
Time must equal the setting

±100 milliseconds or 2%, whichever is greater.

Step 17. Set OVERVOLTAGE 2 TIME DIAL to 010. Monitor the output terminals indicated in Figure 5-1

for OVERVOLTAGE 2. Remove, and then reapply the overvoltage at case terminals 6 and 7.
Observe the time registered by the counter. Time must equal the setting

±100 milliseconds or

2%, whichever is greater.

Step 18. Set OVERVOLTAGE 2 TIME DIAL to 100. Monitor the output terminals indicated in Figure 5-1

for OVERVOLTAGE 2. Remove, and then reapply the overvoltage at case terminals 6 and 7.
Observe the time registered by the counter. Time must equal the setting

±100 milliseconds or

2%, whichever is greater.

Step 19. Set OVERVOLTAGE 2 TIME DIAL to 999. Monitor the output terminals indicated in Figure 5-1

for OVERVOLTAGE 2. Remove, and then reapply the overvoltage at case terminals 6 and 7.
Observe the time registered by the counter. Time must equal the setting

±100 milliseconds or

2%, whichever is greater.

Figure 5-2. Typical Test Setup Timing Options D1 or D2

5-4

BE1-59NC Testing

9279400990 Rev D