5 routing and shielding the bus cable, 6 bus termination, 7 second address setup – Bronkhorst EtherCAT User Manual

Page 11: Outing and shielding the bus cable, Us termination, Econd, Ddress setup

Advertising
background image

BRONKHORST

®

3.5

R

OUTING AND SHIELDING THE BUS CABLE

Only use shielded cables and connection elements that also meet the requirements of category 5, class 2 according to

IEC11801, edition 2.0.

Correct shielding of the bus cable attenuates electrical interference that may occur in industrial environments. The

following measures ensure the best possible shielding:

Manual tighten the mounting screws on the connectors, modules, and equipotential bonding conductors.

Use only connectors with a metal housing or a metalized housing.

Connect the shielding in the connector over a wide surface area.

Apply the shielding of the bus cables on both ends.

Route signal and bus cables in separate cable ducts. Do not route them parallel to power cables (motor leads)

Route the signal cable and the corresponding equipotential bonding, if necessary, close to each other using

the shortest possible route.

Route the bus cable closely along existing grounding surfaces.

In case of fluctuations in the ground potential, a compensating current may flow via the bilaterally

connected shield that is also connected to the protective earth (PE). Make sure you supply adequate

equipotential bonding in such a case.

3.6

B

US TERMINATION

A bus terminator (e.g. using bus terminating resistors) is not necessary. If no follow-up unit is connected to an

EtherCAT unit, this is automatically detected.

3.7

S

ECOND

A

DDRESS SETUP

EtherCAT supports the use of a Second Address. Bronkhorst instruments have 3 rotary switches, with which a Second

Address can be set in the range of 0 – 4095 (0xFFF).

This value of the rotary switches will be copied to the Configured Station Alias register (address 0x0012:0x0013) at

instrument start-up.

Page 11

EtherCAT interface

9.17.063

Advertising