Index sub index description dde parameter – Bronkhorst EtherCAT User Manual

Page 22

Advertising
background image

BRONKHORST

®

Index Sub

Index

Description

DDE parameter

0x6415

0

CO Physical unit controller output

-

1

CO Physical unit controller output

-

0x6420

0

CO Setpoint switch W/W2

-

1

CO Setpoint switch W/W2

-

0x6421

0

CO Automatic / manual mode A/M

-

1

CO Automatic / manual mode A/M

-

0x6422

0

CO Controller on / off

-

1

CO Controller on / off

- (is described above)

0x6423

0

CO Controller mode

-

1

CO Controller mode

Control mode

0x6425

0

CO Control byte

-

1

CO Control byte

- (is described above)

0x6425

0

CO Status word

-

1

CO Status word

- (is described above)

0x7400

0

CO Effective current value Xeff (INT)

-

1

CO Effective current value Xeff (INT)

fMeasure

3

0x7401

0

CO Effective setpoint Weff (INT)

-

1

CO Effective setpoint Weff (INT)

fSetpoint

5

0x7402

0

CO Setpoint W (INT)

-

1

CO Setpoint W (INT)

fSetpoint

5

0x7403

0

CO 2

nd

Setpoint W2 (INT)

-

1

CO 2

nd

Setpoint W2 (INT)

-

0x7404

0

CO Lower setpoint limit W0 (INT)

-

1

CO Lower setpoint limit W0 (INT)

Capacity 0% (read only)

5

0x7405

0

CO Upper setpoint limit W100 (INT)

-

1

CO Upper setpoint limit W100 (INT)

Capacity (read only)

5

The value of object 0x6407:01 CO Decimal digits current value / set point is determined and optimized

automatically during instrument power-up.

5

Examples:

fMeasure = 1.15 ln/min

object 0x6407:01 CO Decimal digits current value / set point = 3

object 0x7401:01 CO Effective current value Xeff = 1.15 x (10 x 10 x 10) = 1150

object 0x6407:01 CO Decimal digits current value / set point = 4

object 0x7402:01 CO Setpoint W (INT) = 22500

fSetpoint = 22500 / (10 x 10 x 10 x 10) = 2.25 ln/min

3

Integer16 value scaled with the value of object 0x6407:01

5

Integer16 value scaled with the value of object 0x6407:01