Specifications

Physical

5.25"W x 5.5"D x 1.75"H (13.3 x 14.0 x 4.5 cm)

Environmental

Temperature

0 - 70 Deg C Operating

Humidity

90 Pct Non Condensing

Power

Wall Mounted Power Supply, included

105 - 240 VAC 50/60Hz or +5VDC direct.

Connections

2 Terminals per Input. (common ground)

Three Terminal per Relay Output (Form C)

LED Indictors

8 x Input.

8 x Output.

Network Link (Link) and Activity (Act).

Remote Unit Link Status (Rmt).

Power (Pwr)

Switch

Reset. Hardware Reset

Inputs

8 Digital Inputs

Dry relay/switch closures or

+/-3VDC to +/-30 VDC

Grounds common

Control Relay

Current Maximums

0.5A @ 120VAC or 1A @ 24VDC

Switching Power

60VA Max 50uW Min

Switching Voltage

120VAC or 60VDC Max 1VDC Min

Switching Current

1A Max 1mA Min

Resistance

100 milliohms (initial value)

Operations

5 Million, mechanical. 100K at maximum load

Network

HTTP Web Server

SSL Secure Sockets Layer

DHCP Assigned or Static IP Address

Email to SMTP Server

SNMP V2 Manageable. MIB Supplied

Inter Device Communications via DxP Protocol supplied.

128 bit AES Encryption optional

Selectable Port assignments for Web, SSL and DxP Protocol.

Advertising