Flowserve CPXS User Manual

Page 6

Advertising
background image

CPXS, CPXNS and CPXPS USER INSTRUCTIONS ENGLISH 71569250 07-11

Page 6 of 48

flowserve.com

in damage or breakage of components and should be
avoided.

NEVER APPLY HEAT TO REMOVE IMPELLER

Trapped lubricant or vapour could cause an explosion.

HOT (and cold) PARTS

If hot or freezing components or auxiliary heating
supplies can present a danger to operators and
persons entering the immediate area action must be
taken to avoid accidental contact. If complete
protection is not possible, the machine access must
be limited to maintenance staff only, with clear visual
warnings and indicators to those entering the
immediate area.

bearing housings must not be insulated and

drive motors and bearings may be hot.

If the temperature is greater than 80 ºC (175ºF) or
below -5 ºC (23 ºF) in a restricted zone, or exceeds
local regulations, action as above shall be taken.

HAZARDOUS LIQUIDS

When the pump is handling hazardous liquids care
must be taken to avoid exposure to the liquid by
appropriate siting of the pump, limiting personnel
access and by operator training. If the liquid is
flammable and or explosive, strict safety procedures
must be applied.

PREVENT EXCESSIVE EXTERNAL

PIPE LOAD
Do not use pump as a support for piping. Do not mount
expansion joints, unless allowed by Flowserve in
writing, so that their force, due to internal pressure, acts
on the pump flange.

NEVER RUN THE PUMP DRY

ENSURE CORRECT

LUBRICATION (See section 5, Commissioning,
startup, operation and shutdown
.)

ONLY CHECK DIRECTION OF

MOTOR ROTATION WITH COUPLING SPACER
PIECE REMOVED
Starting in reverse direction of rotation will damage the
pump.

NEVER EXCEED THE MAXIMUM

DESIGN PRESSURE (MDP) AT THE WORKING
TEMPERATURE OF THE PUMP NAMEPLATE

START THE PUMP WITH OUTLET

VALVE PART OPENED

(Unless otherwise instructed at a specific point in the
User Instructions.)
This is recommended to minimize the risk of
overloading and damaging the pump or motor at full or
zero flow. Pumps may be started with the valve further
open only on installations where this situation cannot
occur. The pump outlet control valve may need to be
adjusted to comply with the duty following the run-up
process. (See section 5, Commissioning start-up,
operation and shutdown
.)

INLET VALVES TO BE FULLY

OPEN WHEN PUMP IS RUNNING
Running the pump at zero flow or below the
recommended minimum flow continuously will cause
damage to the pump.

DO NOT RUN THE PUMP AT

ABNORMALLY HIGH OR LOW FLOW RATES
Operating at a flow rate higher than normal or at a flow
rate with no back pressure on the pump may overload
the motor and cause cavitation. Low flow rates may
cause a reduction in pump/bearing life, overheating of
the pump, instability and cavitation/vibration.

1.6.4

Products used in potentially explosive
atmospheres

Measures are required to:

Avoid excess temperature

Prevent build up of explosive mixtures

Prevent the generation of sparks

Prevent leakages

Maintain the pump to avoid hazard


The following instructions for pumps and pump units
when installed in potentially explosive atmospheres
must be followed to help ensure explosion protection.
For ATEX, both electrical and non-electrical equipment
must meet the requirements of European Directive
94/9/EC. Always observe the regional legal Ex
requirements eg Ex electrical items outside the EU
may be required certified to other than ATEX eg
IECEx, UL.

1.6.4.1

Scope of compliance

Use equipment only in the zone for which it is

appropriate. Always check that the driver, drive
coupling assembly, seal and pump equipment are
suitably rated and/or certified for the classification of
the specific atmosphere in which they are to be
installed.

Advertising
This manual is related to the following products: