DataFlo Digital Electronic Remote Controller DRC17

17

Table 2

Parameter

Minimum

Maximum

Name

Numeric

Numeric

List

Display

Value

Value

Values

Description

Notes

Sec Code

0000

9999

Security code

Unit Adr

1

255

Communications address

Curr Rng

4-20 mA, 0-20 mA

Optional current output module range

P-term

0

9999

Proportional term for controlling algorithm

I-term

0

999

Integral term for controlling algorithm

D-term

0

8000

Derivative term for controlling algorithm

Cyc Intr

1.0 s

999.9 s

Cycle interval

Flt Time

0.8 s

60.0 s

Filtering time window

Bkl Time

0 ms

9999 ms

Gear backlash time

Trq Time

0 ms

9999 ms

Torque time

Dead Bnd

0.1

20.0

Dead band

Action

RISE, FALL

Controller direct (RISE)/reverse (FALL) action

Cyc Res

ON, OFF

Cycle interval reset option

PrLo Alr

-999

999

Process low alarm point

PrHi Alr

-999

999

Process high alarm point

SigErPos

0.0 %

100.0 %

HOLD, IGNORE

Invalid signal position or action

FBErrAct

IGNORE, FULL CW,

Invalid shaft position reading action

FULL CCW

Pon Posn

0.0 %

100.0 %

HOLD

Power-on actuator shaft position

Pon Time

0 s

9999 s

Power-on position dwell time

LoPosLim

0.0 %

100.0 %

Lowest position valve is allowed to reach

2

HiPosLim

0.0 %

100.0 %

Highest position valve is allowed to reach

2

Brk Time

0.10 s

0.99 s

Time motor brake is applied when stopping

CyCount

Valve cycle counter

1

HiPosAlr

0.0 %

100.0 %

Valve shaft high position alarm point

LoPosAlr

0.0 %

100.0 %

Valve shaft low position alarm point

Com Rate

1200, 2400, 4800,

Serial communications bit rate

9600, 19200, 38400

PrLo Eng

-999

999

Process lower value in engineering units

4

PrHi Eng

-999

999

Process upper value in engineering units.

4

SpLo Eng

-999

999

Setpoint lower value in engineering units

3

SpHi Eng

-999

999

Setpoint upper value in engineering units

3

Dflt Val

YES, NO

Option to default all programmable parameters

NOTES

1. The cycle counter cannot be programmed. It can be cleared in the Program Mode by editing the value and pressing both the

and

keys

simultaneously. 2. This parameter restricts valve movement to between the two values. The lower shaft limit must be less than the upper shaft
limit. 3. The setpoint limit must lie within the range of the Process Engineering Units. 4. When the process lower and upper value are edited,
pressing both the

and

keys simultaneously will change the system decimal point. The possibilities for decimal point location are xxx, xx.x,

x.xx, and 0.xxx.