System malfunctions – Flowserve NRR 2-40 User Manual

Page 24

Advertising
background image

24

System Malfunctions

– continued –

The four indicator LEDs flash slowly.

High/low-level alarm

Fault:

The max. admissible temperature in the electrode terminal box is exceeded.

Remedy: Insulate electrode flange to protect the equipment against heat radiation.

The four indicator LEDs flash rapidly.

High/low-level alarm

As soon as the temperature drops below the max. admissible limit the equipment
automatically returns to normal operation.

Fault:

The CAN bus line between the bus-based devices is interrupted.

Remedy: Check wiring and terminals. Restart system.

Fault:

Incorrect node ID(s).

Remedy: Set correct nodes ID(s), referring to section “Annex - assigning and

changing the node IDs”. Disconnect the system from its power supply.
After 5 sec. apply power and restart system.

System malfunction 1

System malfunction 2

LEDs flash slowly

LEDs flash rapidly