Flowserve NRR 2-40 User Manual

Page 9

Advertising
background image

9

Technical Data

Type approval no.
NRR 2-40: TÜV

.

98-399

Input / Output
Interface for CAN bus to DIN ISO 11898 CANopen
Feedback potentiometer 1000

Output – voltage supply for electrodes
Power supply 24 V DC, short-circuit protected.
Analogue output 4 – 20 mA, load 500

for display of actual value (option).

Analogue control output for manipulated variable 4 – 20 mA, max. load 500

(option).

4 volt-free relay contacts.
Max. contact rating with switching voltages of 24 V AC, 115 V AC and 230 V AC:
4 A resistive, 0.75 A inductive at cos

ϕ

0.5

Max. contact rating with a switching voltage of 24 V DC: 4 A.
Contact material: silver, hard-gold plated

Interference suppression
Provide contactor with an external RC combination (100

/ 47 nF)

Relay de-energizing delay
Output “

MIN

”, “

MAX

” 3 s

Indicators and adjustors
1 red LED for switchpoint “

MAX

1 red LED for switchpoint “

MIN

2 green LEDs for “

CONTROL

VALVE

OPENING

” and “

CONTROL

VALVE

CLOSING

1 green LED “

OPERATION

1 red LED “

BUS

MALFUNCTION

1 ten-pole code selector switch for setting node ID and baud rate
4 pushbuttons

Proportional band X

p

1 % to 100 %

Valve position feedback
0

to 1000

(only when used as three-position stepping controller)

Switching range (dead band) X

Sh

0 % (factory setting) up to 15 %

Supply voltage
230 V ± 10 %, 50/60 Hz
115 V ± 10 %, 50/60 Hz (option)

Power consumption
10 VA
Protection
Case:

IP 40 to DIN ISO 60529

Terminal strip:

IP 20 to DIN ISO 60529

Admissible ambient temperature
0 °C to 55 °C

Case material
Front panel: polycarbonate, grey
Enclosure: polycarbonate, black

Weight
Approx. 0.8 kg

Advertising