Ventilation requirements, Clearances, Ventilation heights – Dometic RM2852 User Manual

Page 4: Minimum ventilation heights

Advertising
background image

- 4 -

CLEARANCES

Minimum clearances (in inches) to combustible materials:
Top (G)

0

Side (K)

0

Bottom (L)

0

Rear (M

1

)

0 / 1

(

RM2351 & RM2354

)

1

M: The distance between the rearmost part of the refrigerator and the

wall behind it.

General view. Features may vary according to model.

VENTILATION HEIGHTS

It is essential that all maximum or minimum dimensions are

strictly maintained, as the performance of the refrigerator is de-

pendent on adequate fl ow of air over the rear of the refrigerator.

Minimum ventilation heights

Roof vent and

lower side vent

Upper and lower

side vent

RM2351

RM2354

inches

mm

inches

mm

31

787

34

864

RM2451

RM2454

37-3/4

960

RM2551

RM2554

44-1/2

1130

RM2652

RM2662

RM2663

57-3/4

1465

RM2852

RM2862

RM3862

NDR1062

63-3/4

1620

A

B

B

Minimum

ventilation

height

Condenser

Condenser

Condenser

Condenser

Condenser

A

Condenser

Condenser

Condenser

Condenser

Condenser

Condenser

The upper vent

should be centered

over the condenser

coil at the back of

the refrigerator.

Minimum

ventilation

height

VENTILATION REQUIREMENTS