NOTE

Apply a vacuum to the High Port and the 4-20 mA
transmitter will track the span of the pressure range.
i.e. The Sure-Aire controller with a pressure sensor
of 0 - 41.51 in. W.C. installed, 4.00 mA = 0 in. W.C.,
20.00 mA = 41.52 in. W.C.

WARNING

Due to load resistance change from product to
product, it may be necessary to recalibrate the
4-20 mA transmitter.

4-20 mA Transmitter Calibration
Procedure

1.0 Test Equipment

1.1 Digital Multimeter. Set multimeter to read

mA DC

1.2 Load resistor. Select a series Load Resistor

between 200 and 900 ohms.

2.0 Interconnect Wiring

100 to 240 Vac

50/60 Hz

Input Power

Earth Ground

Line

Neutral

3/8 A 250 Vac

MEDIUM LAG

1

2

3

TB1

4 to 20 mA/
2-10 Vdc (+)

4 to 20 mA/
2-10 Vdc (-)

Shield

Temperature

Sensor

Load Resistance

200-900 Ohms

1

2

3

TB2

4

5

2.1 Validate the controller is setup for 4-20 mA output

signal.

2.2 Validate the power is off on the DC power supply

and the Sure-Aire controller.

2.3 Validate the multimeter is set to read mA DC.

2.4 Select a series Load Resistor between 200 and

900 ohms and install one end to TB2-1.

2.5 Interconnect the multimeter (+) probe to the other

end of the load resistor.

2.6 Interconnect the multimeter (-) probe to TB2-2 to

complete the current loop.

2.7 Apply power to the Sure-Aire controller.

2.8 Press the Setup button on the Touch Panel

interface.

2.9 Keep pressing Next button until you reach the

Transmitter Min Value screen.

2.10 Press Edit, then Inc or Dec until the digital

multimeter reads exactly 4.00 mA.

2.11 Press Enter to store the new value.
2.12 Press Next.

2.13 Transmitter Max Value.

2.14 Press Edit, then Inc or Dec until the digital

multimeter reads exactly 20.00 mA.

2.15 Press Enter to store the new value.

2.16 Press Exit to return to the main screen.

2.17 4-20 mA transmitter calibration completed.

Greenheck

Sure-Aire V 1.00

0.0010

CFM

3.96

mA

Setup

Up

Down

Home

Sure-Aire Controller

LCD Touch Display

Greenheck

Sure-Aire V 1.00

Transmitter Min Value:

1827

Exit

Inc

Dec

Enter

Greenheck

Sure-Aire V 1.00

Transmitter Max Value:

720

Exit

Inc

Dec

Enter

®