Temperature sensor, Specifications – Greenheck High Voltage (100-240 VAC) Sure-Aire Pressure Controller (475742) User Manual

Page 7

Advertising
background image

7

Sure-Aire™ Flow Monitoring System

Temperature Sensor

Interconnect the remote temperature sensor by
connecting the temperature sensor to pins 4 and 5 of
TB2. The Remote Temperature Sensor will adjust the
air density value in the controller based on the sensor
measurement when Temperature Compensation is set
to ‘Yes’. This density compensation will affect the flow
rate accordingly. If Temperature Compensation is set to
‘No’, the air density value will be a function of standard
air (70°F/21°C).

Specifications

Service: Air and non-combustible,

compatible gases

Enclosure Rating: NEMA-4 and IP56

Dimensions: 5 x 5-3/8 x 2-1/2 inches

(127 x 136.5 x 63.5 mm)

Mounting: Mount unit in vertical plane

with #8-32 screws
(4 hole locations)

Accuracy: ±0.5% full pressure scale at

77°F (25°C)

Thermal Effects: 0.015% / °F (0.027% / °C) from

-13° thru 185°F (25° thru 85°C)

Stability: < ±1% per year

Max. Pressure Limit: 72 psi (1993 inches W.C.)

Temperature Limits: 32° to 140°F (0 to 60°C)

Power Requirements: 100 to 240 Vac at 50/60 Hz

Power Consumption: Power = 3VA

Output

Signal: User selectable. 4-20 mA (900

ohms max.) or 2-10 Vdc

Connections: Euro-type removable terminal

blocks with 1/2 inch watertight
conduit fittings.

Pressure Connections: 1/4 inch quick connect

Weight: 1.5

lbs.

Agency Approvals: ETL