Field service checklist – Greenheck Maxitrol Series 14 User Manual

Page 4

Advertising
background image

6.

Replace modulator head if not approximately 45-55 ohms for M611 Valve and 60-80 ohms

for MR212 Valve.

7.

Clean or replace plunger if necessary. Install as per diagrams page 3.

1

7

.

If flame stabilizes, adjust sensitivity control to maintain an even flame.

1

8

.

If the flame is steady throughout the entire modulating range, the TS114 must be moved.

1

9

.

If smooth operation results, isolate effected wiring from source of induced voltage.

2

0

.

If erratic or unstable D.C. voltages are obtained throughout the modulating range, the

amplifier may be assumed faulty. Replace. If erratic operation is noted only over a small

range of 2 or 3 volts, the voltage source may contain surges. Consult Maxitrol.

2

1

.

Sensed temperature will vary from TD114 dial settings. This is intentional.

2

2

.

Correct wiring.

2

3

.

See calibration procedure.

2

4

.

Move TS114 to location where average representative temperature can be sensed.

2

5

.

TD114 dial setting, then check thermostat setting and/or check wiring for shorts.

1.

Modulating valve improperly installed (or see

Symptom ‘L’).

7.

Plunger missing, jammed or improperly

installed.

1

0

.

Short circuit in TD114 Remote Temperature

Selector circuit or wiring.

1

1

.

Open circuit in TS114/TS10765. Discharge or

Inlet Air Sensor Circuit or wiring.

1

2

.

Jumper not connected across amplifier

terminals 2 and 3.

1

3

.

Foreign object holding valve open.

1

4

.

Plunger jammed.

1

5

.

Inlet pressure too low.

1

6

.

Incorrect outlet pressure adjustment of

Pressure Regulator.

1

7

.

Hunting.

1

8

.

Erratic air patterns or improper TS114 location.

1

9

.

Wiring is run next to high voltage switching

circuits causing induced voltages.

2

0

.

Faulty Amplifier or erratic voltage supply.

2

1

.

Inlet Air Sensor is used.

2

2

.

Incorrect Wiring.

2

3

.

System out of calibration.

2

4

.

Improper TS114 location.

2

5

.

Room Override Thermostat circuit closed.

1.

Install properly.

2.

Prove the power source.

3.

Tighten connections or replace wiring.

4.

If modulating voltages are obtained, Check TS114 circuit for shorts. Replace TS114 if

necessary.

5.

If items 2, 3, and 4 check out and modulating voltages are still not obtained, amplifier

may be assumed faulty. Replace.

8.

Adjust to proper minimum fire.

9.

If reading is greater than 1.5” negative pressure, check for clogged filters or other

inlet air restrictions. Consult factory for other solutions.

1

0

.

Correct wiring if shorts exist.

1

1

.

If modulating voltages are obtained, check TS114/TS10765 for open circuits. Replace

TS114/TS10765.

1

2

.

Correct the wiring.

1

3

.

Clean seat. Clean valve or replace if necessary.

1

4

.

Clean, or if necessary, replace plunger.

1

5

.

Increase inlet pressure if possible.

1

6

.

See valve adjustments on page 8.

1.

Arrow on side of Valve should point in direction of gas flow.

2.

Check for 24V AC at amplifier terminals 7 and 8.

3.

Inspect for loose or broken wires between amplifier terminals 1and 2, and TD114

terminals 1 and 2, and TD114 terminals 1 and 3.

4.

Connect test resistor as described in Preliminary Circuit Analysis. Follow procedure

outlined.

5.

Check items 2, 3 and 4.

6.

Measure resistance across modulator terminals with connecting wires detached.

7.

Inspect. Plunger should be installed per diagrams page 3 and operate freely in solenoid

sleeve.

1

0

.

Inspect for shorts at or between Amplifier terminals 1 and 2 or TD114 terminals 1 and 3.

1

1

.

Check TS114/TS10765 for open internal circuit. Connect test resistor as described

in Preliminary Circuit Analysis. Follow procedure outlined.

1

2

.

Inspect.

1

3

.

Remove bottom plate and inspect valve and seat.

1

4

.

Inspect. Plunger should be smooth, clean, and operate freely in solenoid sleeve.

1

5

.

Read pressure at inlet to modulating valve using a manometer with unit operating at full

fire. Pressure should be equal to the sum of outlet pressure

setting plus pressure drop of

the valve (see Maxitrol Capacity Chart).

1

6

.

Read manifold pressure using manometer and compare with recommendation of

equipment manufacturer.

1

7

.

Adjust sensitivity control counter-clockwise.

1

8

.

Connect test resistor as described in Preliminary Circuit Analysis. Turn TD114 selector dial

so heater goes through its entire modulating range.

1

9

.

Temporarily wire each of TD114, TS114, and MR212 externally and observe heater/

equipment operation.

2

0

.

With test resistor connected (per Item #18) and TD114 locally connected (per item#19),

turn TD114 selector dial through entire modulating range. Observe D.C. voltage across

modulator terminals.

2

1

.

Inlet Air Sensor changes 1

0

for each 3.5

0

, 5

0

, or 8

0

outside temperature change from 60

0

(predetermined – turndown varies with model used).

2

2

.

Check wiring diagrams page 7.

2

3

.

Sensed temperature (thermometer next to TS114) does not correspond to TD114 setting.

2

4

.

Sensed temperature (thermometer next to TS114) does not represent average

discharge

air

temperature.

2

5

.

Remove Override Thermostat lead from terminal 2 of TD114.

2.

Short circuit or no voltage to the amplifier.

3.

Open circuit in TD 114. Remote Temperature

Selector circuit or wiring.

4.

Short circuit in TS114, Discharge Air Sensor

circuit or wiring.

5.

Faulty amplifier.

8.

See valve adjustments on page 8.

9.

Close main gas supply and measure manifold pressure with blower operating.

Reading should be less than 1.5” w.c. negative pressure.

6. Short circuit or open circuit in Modulator Coil.

9.

Excessive negative burner pressure.

8.

Incorrect by-pass metering valve adjustment.

SYMPTOM

POSSIBLE CAUSE

FIELD TEST

REMEDY

No gas flow.

Continuous

Low Fire (electronics

problem).

Continuous Low

Fire (electronics OK).

Incorrect Minimum

Fire Erratic or

Pulsating Flame.

Continuous High

Fire (electronics

problem).

Continuous High

Fire (electronics OK).

Incorrect Maximum

Fire.

Erratic or Pulsating

Flame.

Incorrect Discharge

Air Temperature.

A

.

Field Service Checklist

Burned out

Transformer.

2

6

.

Short circuit in modulator coil.

2

7

.

Short circuit between amplifier and modulator

valve.

2

6

.

Measure resistance across modulator terminals with red lead wires disconnected.

2

7

.

Inspect wiring.

2

6

.

Replace modulator head if less than 40 ohms.

2

7

.

Correct wiring is short is found.

Discharge Air

Temperature too

Low when T115 is

operative.

2

8

.

Too low an Override Temperature setting.

2

9

.

Burner capacity may be insufficient.

2

8

.

Check “Override Temperature Selector” of TD114.

2

9

.

Check for high fire (Maximum manifold pressure specified for heater).

2

8

.

Reset to correct temperature.

2

9

.

If on high fire, control can do no more. Heater unable to furnish additional heat to raise

temperature.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

©2007 Maxitrol Comp

an

y,

All Right

s Reserved

4

Advertising